background image

4

2.1  Controls

The BA327C and BA328C are controlled and
calibrated via four push-button switches.    In the
display mode these switches have the following
functions:

P

While this button is pushed the
indicator will display the input current in
mA, or as a percentage of the
instrument span depending upon how
the indicator has been programmed.
When the button is released the normal
display in engineering units will return.
The function of this push-button is
modified when alarms or a tare function
are fitted to the indicator.

Down

While this button is pushed the
indicator will display the number which
the indicator has been calibrated to
display with a 4mA input.  When
released the normal display in
engineering units will return.

Up

While this button is pushed the
indicator will display the number which
the indicator has been calibrated to
display with a 20mA input.  When
released the normal display in
engineering units will return.

E

No function in the display mode.

3. INTRINSIC SAFETY CERTIFICATION

3.1 ATEX certificate

The BA327C and BA328C have been issued with
an EC-Type Examination Certificate number
ITS02ATEX2028 by Notified Body ITS Testing and
Certification Ltd.  This confirms compliance with
the European ATEX Directive for Group II,
Category 1G equipment, EEx ia IIC T5.   The
instruments bear the Community Mark and, subject
to local codes of practice, may be installed in any
of the European Economic Area (EEA) member
countries.    ATEX certificates are also acceptable
for installations in Switzerland.  This manuals
describes installations which conform with
EN60079:Part 14.  When designing systems for
installation outside the UK th local Code of
Practice should be consulted.

3.2   4/20mA input

In Europe, sources of energy which do not
generate more than 1.5V; 100mA, or 25mW are for
intrinsic safety purposes considered to be simple
apparatus
.
Although the BA327C and BA328C indicators do
not themselves comply with the requirements for
simple  apparatus, the EC-Type Examination
Certificate specifies that under fault conditions the
voltage, current and power at the 4/20mA input
terminals 1 & 3 will not exceed those specified for
simple apparatus.    This allows the BA327C and
BA328C  to be connected into any intrinsically safe
circuit protected by a EEx ia IIC certified Zener
barrier or galvanic isolator providing the output
parameters of  the circuit do not exceed:

Uo

=

30V dc

Io

=

200mA

Po

=

0.85W

The EC-Type Examination Certificate specifies that
the maximum equivalent capacitance and
inductance between the two 4/20mA  input
terminals 1 and 2 is:

Ci

=      20nF

Li

=      10µH

To determine the maximum permitted cable
parameters, these figures should be subtracted
from the maximum cable capacitance and
inductance permitted by the certificate for the loop
into which the indicator is installed.

3.3  Zones, gas groups and T rating

The BA327C and BA328C have been certified EEx
ia IIC T5.   When connected to a suitable system
the indicator may be installed in:

Zone 0 explosive gas air mixture

continuously present.

Zone 1 explosive gas air mixture likely

to occur in normal operation.

Zone 2 explosive gas air mixture not

likely to occur, and if it does
will only exist for a short time.

Summary of Contents for BA327C

Page 1: ...BA327C BA328C intrinsically safe loop powered 4 digit panel mounting indicators issue 11 Issue 11 3rd November 2009...

Page 2: ...rator 8 Maintenance 8 1 Fault finding during commissioning 8 2 Fault finding after commissioning 8 3 Servicing 8 4 Routine maintenance 8 5 Guarantee 8 6 Customer comments 9 Accessories 9 1 Scale card...

Page 3: ...lt conditions the voltage current and power at the input terminals of each instrument will not exceed those specified for simple apparatus in Clause 5 4 of EN50020 1994 The BA327C and BA328C are also...

Page 4: ...allations in Switzerland This manuals describes installations which conform with EN60079 Part 14 When designing systems for installation outside the UK th local Code of Practice should be consulted 3...

Page 5: ...s BEKA associates name and location Non European certification information may also be shown 4 SYSTEM DESIGN FOR HAZARDOUS AREAS 4 1 Transmitter loops BA327C and BA328C indicators may be connected in...

Page 6: ...iers a two channel Zener barrier or a galvanic isolator must be used Again it is necessary to ensure that the voltage capability of the 4 20mA signal is sufficient to drive the indicator plus the volt...

Page 7: ...erall dimensions of each instrument and the required panel cut out dimensions To achieve an IP65 seal between the instrument enclosure and the instrument panel the smaller tolerance aperture must be u...

Page 8: ...3 EMC The BA327C and BA328C comply with the requirements of the European EMC Directive 2004 108 EEC For specified immunity all wiring should be in screened twisted pairs with the screens earthed with...

Page 9: ...ating decimal points for a few seconds while the new information is stored in non volatile memory All new BA327C and BA328C indicators are supplied calibrated as requested at the time of ordering If c...

Page 10: ...10...

Page 11: ...lowing table shows the output current from a non linearised differential flowmeter of full flow Current output mA 2 5 4 01 10 0 4 16 25 0 5 00 50 0 8 00 75 0 13 00 100 0 20 00 6 3 Resolution rESn This...

Page 12: ...orrect pressing P will transfer control to the next digit When the least significant digit has beenadjusted press E to return to the SPAn prompt followed by E to return to the menu 6 7 Conditioning su...

Page 13: ...calibration and conditioning of the instrument may be protected by a four digit security code which must be entered before access to the programme menu is granted New instruments are programmed with...

Page 14: ...Down buttons select 50 and then press E twice to return to the main menu Step 5 Define function of P push button Select C P from the main menu and press P to reveal the function of the P button in the...

Page 15: ...to the main menu Step 4 Define function of P push button Select C P from the main menu and press P to reveal the function of the P button in the display mode Select 4 20 and return to the main menu by...

Page 16: ...ing correctly the following procedure should be followed Symptom Cause Solution No display No power Check that current 0V between supply is flowing in the loop terminals 1 and 3 Unstable 4 20mA input...

Page 17: ...ependently programmed as high or low alarms with normally open or normally closed outputs Fig 8 illustrates the conditions available and shows which are fail safe i e in the alarm condition the output...

Page 18: ...18...

Page 19: ...mmable alarm functions Display Description of function EnbL Alarm enable Enables or disables the alarm function without changing the alarm parameters See section 9 3 4 SP1 Alarm setpoint 1 Adjusts the...

Page 20: ...y pressing the Up or Down button followed by the E button to return to the alarm menu 9 3 8 Hysteresis HStr During programming hysteresis is shown in the units the indicator has been calibrated to dis...

Page 21: ...security code allowing direct access to the setpoints by pressing the P and Up buttons simultaneously New instruments with alarms are supplied with this function disabled and the security code set to...

Page 22: ...using the Add and dEL functions In both these functions the indicator initially displays the current break point and the total number of break points being used e g 5 13 current total number of break...

Page 23: ...f break points Each subsequent operation of the P push button will introduce an additional break point When adding a break point to a calibrated indicator the insertion position can be selected using...

Page 24: ...24...

Page 25: ...e output which enhances daylight viewing but an additional IS interface and field wiring are required 9 6 1 Separately powered backlight The separately powered backlight is segregated from the measuri...

Page 26: ...is loop powered This eliminates the need for a separate Zener barrier or galvanic isolator and associated wiring for the backlight thus significantly reducing the installation cost As shown in Fig 16...

Page 27: ...3 A1 2 4 20mA input in nonincendive circuit The BA327C and BA328C are also Factory Mutual approved as nonincendive for Class I Division 2 locations which allows both indicators to be installed in Div...

Page 28: ...between the backlight and the measuring circuits should be maintained by following the wiring methods recommended in ANSI NFPA70 article 504 See Fig 15 A1 3 2 2 Loop powered backlight This backlight h...

Page 29: ...29...

Page 30: ...30...

Page 31: ...31...

Page 32: ...f Conformity number IECEx ITS 05 0003 which specifies the following certification code and marking Ex ia IIC T5 Ta 40o C to 60 o C The specified intrinsic safety parameters are identical to the ATEX s...

Reviews: