The BA337E and BA338E EC-Type Examination
Certificate specifies that the maximum capacitance
and inductance that may be safely connected to the
energised pulse input terminals 5 & 6 (terminals 3 & 4
linked) is:
Co
=
2.4µF
Lo
=
200mH
This is not restrictive as the combined capacitance
and inductance of most sensors and the connecting
cable will be less than this.
3.6
Remote reset terminals
The BA337E and BA338E total display may be reset
to zero by connecting the external reset terminals
RS1 and RS2 together for more than one second.
The two reset terminals have the following input and
output safety parameters:
Uo
=
3.8V dc
Io
=
1mA
Po
=
1mW
Ui
=
28V dc
Ii
=
200mA dc
Pi
=
0.84W
The equivalent capacitance and inductance between
them is:
Ci
=
0
Li
=
0
The maximum cable capacitance and inductance that
may be safely connected between the reset terminals
RS1 and RS2 is:
Co
=
40µF
Lo
=
1H
The reset terminals may be directly connected to any
mechanically operated switch located within the same
hazardous area as the BA337E or BA338E Rate
Totaliser.
The switch and associated wiring should
be able to withstand a 500V rms insulation test to
earth.
If the reset switch is required in the safe area a Zener
barrier or intrinsically safe relay is required to transfer
the contact closure into the hazardous area. Almost
any intrinsically safe relay with certification permitting
the contacts to be connected to equipment in the
hazardous area may be used.
A positive polarity
Zener barrier may also be used as shown in Fig 2.
Alternatively the BA337E or BA338E may be
configured so that the total display is reset to zero
when the
&
and
*
push buttons are operated
simultaneously for more than three seconds.
See
6.19
3.7 Certification label information
The Rate Totaliser certification information label is
fitted in a recess on the top outer surface of the
enclosure.
It shows the ATEX and IECEx
certification information plus BEKA associates name,
location, year of manufacture and the instrument
serial
number.
Non
European
certification
information may also be included.
BA337E Certification information label
9
Summary of Contents for BA337E
Page 4: ...4 ...
Page 22: ...22 ...
Page 23: ...23 ...
Page 30: ...30 ...
Page 41: ...41 ...
Page 50: ...50 ...
Page 51: ...51 ...
Page 52: ...52 ...
Page 53: ...53 ...
Page 54: ...54 ...
Page 55: ...55 ...
Page 56: ...56 ...
Page 57: ...57 ...
Page 58: ...58 ...
Page 59: ...59 ...
Page 60: ...60 ...
Page 61: ...61 ...