background image

27

9.2.5  Type of alarm:  tYPE

This function conditions the alarm to operate on
the rate or total display.   Alarm 1 and Alarm 2 may
both be conditioned as rate or total alarms, or one
may be conditioned for rate and the other for total.

To check or change the type of alarm, select 'tYPE'
from the alarm menu and press 

P

 which will reveal

the current setting.  The function can be changed
by pressing the 

Up

 or 

Down

 button followed by the

E

 button to return to the alarm menu.

Note: 

 To prevent accidental conditioning the

alarm must be re-enabled after the alarm Type has
been changed.

9.2.6  Setpoint adjustment:   SPx1 and SPx2

The rate alarm setpoints SPr1 and SPr2 may be
positioned anywhere between 0 and 20000
providing this corresponds to an input current
between 3.8 and 20.2mA.   The total alarm
setpoint SPt1 and SPt2 may be positioned
anywhere between 00000000 and 99999999

To adjust the setpoint select 'SPr1' or 'SPt1' from
the alarm menu and press 

P

 which will reveal the

existing alarm setpoint.  Each digit of the setpoint
can be adjusted using the 

Up

 and 

Down

 push-

buttons, and the 

P

 button to move to the next digit.

When the required setpoint has been entered
press 

 to return to the alarm menu.

9.2.7  Alarm function:   HI.LO

Each alarm can be conditioned as a high or low
alarm.   To check or change the alarm function
select 'HI.LO' from the alarm menu and press 

P

 to

reveal the current setting.  The function can be
changed by pressing the 

Up

 or 

Down

 buttons

followed by the 

E

 button to return to the alarm

menu.

9.2.8  Alarm output status:   no.nc

This function allows the alarm output to be open or
closed in the alarm condition.  When deciding
which is required, care must be taken to ensure
that the alarm output is fail safe.    See Fig 9.

CAUTION

When the 4/20mA supply is removed
both alarm outputs will open irrespective
of conditioning.  Therefore for fail safe
operation both alarm outputs should be
programmed to be open in the alarm
condition.

To check the alarm output status select 'no.nc'
from the alarm menu and press 

P

 to reveal the

current setting.  The function can be changed by
pressing the 

Up

 or 

Down

 button followed by the 

E

button to return to the alarm menu.

9.2.9  Hysteresis:   HStr

Hysteresis is only available on rate alarms.  During
programming hysteresis is shown in the units of
rate the BA354ND has been calibrated to display.
To adjust the hysteresis, select 'HStr' from the
alarm menu and press 

P

 which will reveal the

existing figure.  Each digit can be adjusted using
the 

Up

 and 

Down

 push-buttons, and the 

P

 button

to move to the next digit.  When the required
hysteresis has been entered, press 

to return to

the alarm menu.
e.g.  A BA354ND calibrated to display a flow of 0
to 5000, with a high alarm set at 4000 and
hysteresis of 100 will perform as follows:

High alarm will be activated when flow
equals or exceeds 4000, but will not reset
until the flow falls below 3900.

9.2.10  Alarm delay:   dELA

This function enables activation of the alarm output
to be delayed for a fixed time following the alarm
condition occurring.  The delay can be
programmed in 1 second increments up to 3600
seconds.  If a delay is not required zero should be
entered.  To adjust the delay select 'dELA' from the
alarm menu and press 

P

 which will reveal the

existing delay.  Each digit of the delay can be
adjusted using the 

Up

 and 

Down

 push-buttons,

and the 

P

  button to move to the next digit.  When

the required delay has been entered, press 

to

return to the alarm menu.
The alarm annunciator will start flashing
immediately an alarm occurs and continue for the
delay time after which the alarm output will be
activated.

9.2.11  Alarm silence time:   SIL

This function is primarily intended for use in small
installations where the alarm output directly
operates an annunciator such as a sounder.
When the alarm silence time is set to any figure
other than zero, the 

P

 push-button becomes an

alarm accept button.   After an alarm has occurred,
operating the 

P

  button will cause the alarm output

to revert to the non-alarm condition for the
programmed alarm silence time.  The instrument
alarm annunciator will continue to display an alarm
after it has been accepted and silenced.   The
alarm silence time may be adjusted between 0 and
3600 seconds in 1 second increments.

Summary of Contents for BA354ND

Page 1: ...Issue 3 11th November 2009 BA354ND Type n certified 4 20mA loop powered field mounting rate totaliser issue 3...

Page 2: ...e P push button 6 13 Total scale factor 6 14 Percentage clip off 6 15 Local reset of total display 6 16 Security code 6 17 Over and under range 7 Calibration Examples 7 1 Using an external current sou...

Page 3: ...oped across R1 which is proportional to the 4 20mA input current provides the input signal for the analogue to digital converter Each time a 4 20mA current is applied to the instrument initialisation...

Page 4: ...sc in the lower left hand corner indicator of the display rotates when the input current exceeds 4mA 3 TYPE n CERTIFICATION 3 1 Certificate of Conformity ITS Testing and Certification Ltd Formerly ERA...

Page 5: ...mmon industrial gases 3 6 Certification Label Information The ATEX certification label is fitted in a recess on the top outer surface of the enclosure The year of manufacture and instrument serial num...

Page 6: ...gn requirements listed in section 4 1 If suitably certified the flowmeter may also be located in Zone 2 as shown in Fig 3B Both examples show an external reset switch Alternatively the BA354ND may be...

Page 7: ...safe area To prevent circulating currents cable screens should only be earthed at one point in the safe area The BA354ND enclosure is supplied with a bonding plate to ensure electrical continuity bet...

Page 8: ...8 Fig 5 Dimensions and terminal connections...

Page 9: ...s displayed on the five digit display Using the instrument s CAL or SEt functions this display may be calibrated to show the flow rate in engineering units Both the zero display at 4mA and the span di...

Page 10: ...cimal point clip off to adjust value Press or between 0 and 10 or and pressing Define Security Enter by Code to move to next digit Local reset or Fig 7B Programme Structure CLr Gtot E E E E E E E E P...

Page 11: ...arly set the required full scale display accurate 20mA input current scale display using an Similarly set the required full to move to next digit pressing or and set required zero display by With accu...

Page 12: ...l new BA354ND rate totalisers are supplied calibrated as requested at the time of ordering If calibration information is not supplied the BA354ND will be set to display a rate of 0 00 with 4mA input a...

Page 13: ...n and 4 20 to display current See section 6 12 Display Description of function SCALE T Total Scale Factor Defines the arithmetic relationship between the rate and total displays May be adjusted betwee...

Page 14: ...ned press E to return to the main menu If the application requires flow rate to be the primary display i e shown on the large display the d P function enables the rate and total displays to be interch...

Page 15: ...ing the Up and Down buttons and the P button to move to the next digit enter the password SurE Pressing E will then give access to the sub menu Note S is entered as 5 6 9 1 AC rejection FrE WARNING If...

Page 16: ...lay rate display divided by Per second tb 1 1 Per minute tb 60 60 Per hour tb 3600 3600 Select the required divisor and press E to return to the main menu 6 12 Function of the P push button C P This p...

Page 17: ...e of total flow may be adjusted in one percent increments using the Up or Down buttons When set as required press the E button to enter the revised figure and return to the main programme menu 6 15 Lo...

Page 18: ...ing a traceable 4 20mA calibrator Section 7 2 contains an example of calibration using the instruments internal 4 and 20mA references which although not traceable are adequate for many industrial appl...

Page 19: ...significant digit of the total display and following decimal point are flashing i e a resolution of 0 1 Press P to move control to the rate display Using the Up or Down push button move the flashing d...

Page 20: ...12 Reset the grand total to zero To reset the grand total to zero select CLr Gtot from the main menu and press P which will cause the instrument to display Clr no Toggle this to CLr YES using the Up o...

Page 21: ...by simultaneously pressing P and E Assuming a security code has not already been entered the instrument will respond by displaying root which is the first function in the main menu Steps Perform as de...

Page 22: ...8 8 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE Live maintenance should only be performed when there is no risk of a flammable atmosphere being present and dus...

Page 23: ...accessory boards to the terminals should be un plugged The replacement display assembly may then be installed and the enclosure reassembled If after replacement of the display assembly the instrument...

Page 24: ...programmed as high or low rate or total alarms with normally open or normally closed outputs Fig 9 illustrates the conditions available for a rate alarm and shows which are fail safe i e output is in...

Page 25: ...he SCALE t functions and each alarm may be programmed as a rate or a total alarm For simplicity Fig 12 only shows the programmable functions on the rate option of alarm AL1 Alarm 2 and the total optio...

Page 26: ...s setpoint Sub menu which enables direct access to the alarm setpoints from the operating mode and defines a separate security code See section 9 2 12 9 2 4 Alarm enable EnbL This function allows the...

Page 27: ...to reveal the current setting The function can be changed by pressing the Up or Down button followed by the E button to return to the alarm menu 9 2 9 Hysteresis HStr Hysteresis is only available on r...

Page 28: ...de press E to return to the EnbL prompt followed by the Up or Down button to select the access code prompt AcCd Pressing P will reveal the current security code Each digit of the code may be changed b...

Page 29: ...14 providing the supply voltage is below 30V the backlight safety components will ensure that the input current is less than 100mA Fig 14 Backlight powered by Zener barrier Reducing the supply voltag...

Page 30: ...commissioning 8 1 after commissioning 8 2 Flow indicator 2 2 Flow transmitter loops 4 1 Gas groups 3 5 Grand total 2 1 clear 6 3 6 10 Guarantee 8 5 HI LO 9 2 3 9 2 7 HStr 9 2 3 9 2 9 Input 4 20mA 3 3...

Reviews: