APPENDIX 3
ETL & cETL certification for installations in USA
and Canada.
A3.0 cETL Mark
For installations in the USA and Canada, the
BA384NG Rate Totaliser has ETL and cETL Ex nA
and Ex tc approval, Control Number 4008610.
Copies of the Authorisation to Mark may be down
loaded from the BEKA associates website
www.beka.co.uk or requested from the BEKA
associates sales office.
A3.1 ETL and cETL certification
The US and Canadian standards used for
assessment and certification of the BA384NG are
listed on the cETL Authorisation to Mark.
ETL codes for USA
Class I Zone 2 AEx nA ic IIC T5 Gc
Zone 22 AEx ic tc IIIC T80ºC Dc
Ta = -40°C to 60°C
cETL codes for Canada
Ex nA ic IIC T5 Gc
Ex n IIC T5 Gc
Ex ic tc IIIC T80ºC Dc
Class III Div 2 Class II Div 2 Gp F G
Ta = -40°C to 60°C
The ETL and cETL safety parameters are the same
as ATEX and IECEx parameters, therefore the
systems shown in the main section of this manual
and in Appendix 1 may be used for US and
Canadian installations subject to complying with the
local codes of practice.
The Rate Totaliser's front panel push button contacts
are non incendive and have been certified
intrinsically safe Ex ic, without the need for an
external Zener barrier or galvanic isolator, as shown
on the ETL Authorisation to Mark. This allows the
Rate Totaliser to be adjusted and configured live
when installed in Zone 2 or 22 hazardous areas.