6
4.2 Installation Procedure
a. Insert the BA418CF-F into the instrument
panel cut-out from the front of the panel.
b. Fix panel mounting clips to opposite sides of
the instrument and tighten until the
instrument is secure. Four clips are required
to achieve an IP66 seal between the
instrument enclosure and the panel.
c. Connect the panel wiring to the rear terminal
block as shown in Fig 3. To simplify
installation, the terminals are removable so
that panel wiring can be completed before
the instrument is installed.
Fig 3 Installation and terminal connections
4.3 EMC
The BA418CF-F complies with the requirements of
the European EMC Directive 89/336/EEC. For
specified immunity, all wiring should be in
screened twisted pairs with the screens earthed at
one point in the safe area.