APPENDIX 1
FM approval for use in the USA and
cFM Approval for use in Canada

A1.0  Factory Mutual Approval
For  installations  in  the  USA  and  Canada  the
BA448CF-P  has  FM  and  cFM  intrinsic  safety  and
nonincendive 

approvals, 

project 

identification

3027031  and  3027031C.      Copies  of  the
Certificates  of  Compliance  are  available  from
BEKA 

associates 

sales 

office 

and

www.beka.co.uk.

A1.1  Intrinsic safey  approval
The  BA448CF-P  is  approved  to  FM  Class  3610
intrinsic  safety  standard  for  use  in  hazardous
(classified)  locations.    Installations  must  comply
with  BEKA  associates  Control  Drawing  CI410-12,
which  is  attached  to  this  Appendix,  ANSI/ISA
RP12.06.01  ‘Installation  of  Intrinsically  Safe
Systems for Hazardous (Classified) Locations’ and
with the National Electrical Code ANSI/NFPA70.

Canadian  installations  must  comply  with  the
Canadian  Electrical  Code  C22.2  and  with  BEKA
associates  Control  Drawing  CI410-12  which  is
attached to this Appendix.

The  BA448CF-P  has  a  T4  rating  at  ambient
temperatures  up  to  +70

o

C  and  may  be  used  with

the following gases:

Intrinsic Safety

Division 1 or 2

Class I    Group A & B
               Group C
               Group D

Zone 0, 1 or 2

Class 1   Group IIC
               Group IIB
               Group IIA

The FM and cFM entity parameters are identical to
the  ATEX  parameters  and,  like  the  ATEX
certification, confirm that the BA448CF-P complies
with  the  FISCO  Field  Device  requirements
specified  in  IEC60079-27.    The  intrinsically  safe
system  shown  in  Fig  1  of  this  manual  may
therefore  be  used  for  installations  in  the  USA  and
Canada,  providing  the  fieldbus  power  supply,
terminators,  Zener  barriers  and  galvanic  isolators
are  FM  Approved  for  US  installations  and  cFM  or
CSA  Approved  for  Canadian  installations.    All
installations  must  comply  with  BEKA  associates
Control Drawing CI410-12.

FM and cFM Approval also allows the BA448CF-P
to  be  connected  to  non-FISCO  systems  using  the
entity concept – see section 4.2 of this manual.

A1.2  Nonincendive approval
The  BA448CF-P  is  also  Class  3611  nonincendive
approved  by  Factory  Mutual  allowing  it  to  be
installed  in  Division  2  hazardous  (classified)
locations  without  the  need  for  Zener  barriers  or
galvanic  isolators.      US  installations  must  comply
with  the  BEKA  associates  Control  Drawing  CI410-
13,  which  is  attached  to  this  Appendix,  and  with
the National Electrical Code ANSI/NFPA70.

Canadian  nonincendive  installations  must  comply
with  the  Canadian  Electrical  Code  C22.2  and  with
BEKA associates Control Drawing CI410-13 which
is attached to this Appendix.

The  FM  and  cFM  Nonincendive  Approvals  also
allow  the  BA448CF-P  fieldbus  indicator  to  be
connected  to  any  appropriately  certified  FNICO
compliant fieldbus segment.

The  BA448CF-P  has  a  T4  rating  at  ambient
temperatures  up  to  +70

o

C  and  may  be  used  with

the following gases:

Nonincendive

Division 2

Class I    Group A & B
               Group C
               Group D

Zone 2

Class I    Group IIC
               Group IIB
               Group IIA

Summary of Contents for BA448CF-P

Page 1: ...Supplied by Call us on 44 0 118 916 9420 Email info 247able com com Installation Maintenance Instructions BA448CF P...

Page 2: ...Park Danehill Lower Earley Reading Berkshire RG6 4UT UK Tel 44 0 118 9311188 Email info able co uk Aberdeen Office Unit 6 Airside Business Park Kirkhill Industrial Estate Dyce Aberdeen AB21 0GT UK Tel...

Page 3: ...Issue 2 23 rd June 2011 BA448CF P PROFIBUS PA Intrinsically safe Panel mounting 8 variable Fieldbus Indicator Issue 2...

Page 4: ...ured input parameters 6 4 3 Enter address display parameters 6 4 4 Enable selected input 6 4 5 Enter source address 6 4 6 Enter destination address 6 4 7 Enter Index 6 4 8 Decimal point position 6 4 9...

Page 5: ...es to this manual For additional node configuration information please refer to the BEKA PROFIBUS PA Display Fieldbus Interface Guide which is available from the BEKA sales office or may be downloaded...

Page 6: ...on information The instrument serial number and year of manufacture are shown on the rear panel adjacent to the terminals 4 SYSTEM DESIGN FOR HAZARDOUS AREAS 4 1 FISCO Systems The BA448CF P may be con...

Page 7: ...that even in the event of rare incidents an ignition source due to impact or friction between the aluminium enclosure at the rear of the instrument mounting panel and iron steel is excluded Fig 2 BA4...

Page 8: ...the or button When set as required operating the P button will transfer control to the next digit that may be adjusted in the same way When all digits are set as required operating the E button will...

Page 9: ...BA448CF P listener are not known In the SCAn function pressing the P button causes the BA448CF P listener to search the fieldbus segment to which it is connected for all data sources The hexadecimal...

Page 10: ...8...

Page 11: ...eters Sub menu which allows known fieldbus device addresses to be entered and all display parameters adjusted for each of the eight fieldbus listener inputs See section 6 4 3 Enb Enable selected input...

Page 12: ...source address to the selected input and return the display to the source and destination addresses from which another data source address may be selected When a data source address is allocated to a...

Page 13: ...mode irrespective of the numeric value When positioned as required operating the E button will enter the selection and return to the dP prompt in the edit sub menu 6 4 9 Configuration of bargraph dis...

Page 14: ...evised access code will be activated when the transmitter is returned to the display mode If the access code is lost please contact BEKA associates 6 4 12 Change from fieldbus listener to fieldbus nod...

Page 15: ...y mode 7 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE Live maintenance is permitted on intrinsically safe equipment installed in a hazardous area but only certif...

Page 16: ...a scale for the horizontal bargraph 8 2 Tag number The BA448CF P can be supplied with a thermally printed tag number on the rear panel adjacent to the terminals 8 3 BEKA PROFIBUS PA Display Fieldbus...

Page 17: ...SCO Field Device requirements specified in IEC60079 27 The intrinsically safe system shown in Fig 1 of this manual may therefore be used for installations in the USA and Canada providing the fieldbus...

Page 18: ...16...

Page 19: ...17...

Page 20: ...18...

Page 21: ...19...

Page 22: ...20...

Page 23: ...21...

Page 24: ...22...

Page 25: ...BA448CF P may be installed in Zone 0 explosive gas air mixture continuously present Note Special conditions for safe use apply see above Zone 1 explosive gas air mixture likely to occur in normal oper...

Reviews: