1.  DESCRIPTION
The BA448CF-P fieldbus indicator is an intrinsically
safe,  PROFIBUS  PA  instrument  that  may  be
configured  as  a  fieldbus  node  or  as  a  fieldbus
listener. It can display up to eight fieldbus  process
variables  on  a  five  digit  LCD  and  a  31  segment
analogue  bargraph.      The  instrument  is  bus
powered so no additional power supply is required
and  it  has  PROFIBUS  PA  User  Organisation
approval, certificate Z01505.

Fieldbus  node  configuration  may  be  performed  by
either  a  User  PRM  data  download  or  by  a  DPV1
configurator,  and  if  required,  the  instrument
address  may  be  entered  via  the  front  panel  push
buttons.

When  configured  as  a  fieldbus  listener,  the
BA448CF-P  is  not  visible  to  the  fieldbus  host  and
can  only  be  configured  using  the  push  buttons  on
the front of the instrument.

Housed  in  a  robust  72  x  144  panel  mounting  DIN
enclosure,  the  BA448CF-P  fieldbus  indicator  has
an IP66 front panel and is supplied with a gasket to
seal the joint between the instrument & the panel.

The  instrument  is  intrinsically  safe  and  has  been
certified  by  European  Notified  Body  Intertek
Testing  and  Certification  Ltd  (ITS)  to  the  ATEX
Directive  94/9/EC  for  use  in  explosive  gas
atmospheres.

The  BA448CF-P  also  has  intrinsic  safety  and
nonincendive  FM  and  cFM  Approval  allowing
installation  in  the  USA  and  Canada  –  see
Appendix 1.

For  international  applications  the  BA448CF-P
fieldbus  indicator  has  IECEx  intrinsic  safety
approval  –  see Appendix 2.

The instrument’s communication protocol is shown
on the rear of the instrument.  The ‘-P’ order code
suffix  also  indicates  the  protocol  but  is  not  shown
on  the  instrument  certification  label.      There  is  an
alternative  version  of  the  fieldbus  display,  order
code  BA448CF-F  for  use  on  FOUNDATION™
fieldbus networks.

1.1  Documentation
This  instruction  manual  describes  ATEX  system
design and installation of the BA448CF-P Fieldbus
Indicator.   System design information for FM, cFM
and  IECEx  installations  is  shown  in  separate
appendices to this manual.

For  additional  node  configuration  information
please refer to the BEKA PROFIBUS PA Display –
Fieldbus  Interface  Guide
  which  is  available  from
the BEKA sales office, or may be downloaded from
www.beka.co.uk

2.  OPERATION
The  BA448CF-P  indicator  can  display  up  to  eight
pre-configured  PROFIBUS  PA  process  variables
designated  in-1  to  in-8.      The  operator  can  select
which  variable  is  displayed  using  the 

and 

push  buttons  which  scroll  the  display  through  the
eight  inputs.  A  numeric  annunciator  on  the  left
hand  side  of  the  display  shows  which  of  the  eight
inputs is currently being displayed.

2.1  Error messages

‘no ConF’

No inputs have been
configured or are enabled.

‘no dAtA’

No data is being received
with the current configuration.

3.  INTRINSIC SAFETY CERTIFICATION
3.1 ATEX certificate
The BA448CF-P has been issued with an EC-Type
Examination  Certificate  by  Notified  Body  Intertek
Testing  and  Certification  Ltd  (ITS)  confirming
compliance  with  the  European  ATEX  Directive
94/9/EC  for  Group  II,  Category  1G,  gas
atmospheres,  Ga  Ex  ia  IIC  T4.    The  instrument
bears  the  Community  Mark  and,  subject  to  local
codes  of  practice,  may  be  installed  in  any  of  the
European 

Economic 

Area 

(EEA) 

member

countries.    ATEX  certificates  are  also  acceptable
for installations in Switzerland.

This  manual  describes  ATEX  installations  in
explosive  gas  atmospheres  that  conform  with
EN 

60079:Part14 

Electrical 

Installation 

in

Hazardous  Areas.    When  designing  systems  for
installation  outside  the  UK,  the  local  Code  of
Practice should be consulted.

3.2  Zones, gas groups and T rating
The  BA448CF-P  has  been  issued  with  EC  Type
Examination 

certificate 

ITS06ATEX25314/2X

confirming  that  it  complies  with  the  requirements
for  Group  II  Category  1G  Ga  Ex  ia  IIC  T4  (Tamb
–40  to  70

o

C)  specified  in  the  ATEX  Directive.

When connected to  a suitable certified  system  the
BA448CF-P may be installed in:

Zone 0

explosive gas air mixture
continuously present.
Note:  Special conditions for
safe use apply see section 5.1

Zone 1

explosive gas air mixture
likely to occur in normal
operation.

Zone 2

explosive  gas  air  mixture  not
likely to occur, and if it does will
only exist for a short time.

Summary of Contents for BA448CF-P

Page 1: ...Supplied by Call us on 44 0 118 916 9420 Email info 247able com com Installation Maintenance Instructions BA448CF P...

Page 2: ...Park Danehill Lower Earley Reading Berkshire RG6 4UT UK Tel 44 0 118 9311188 Email info able co uk Aberdeen Office Unit 6 Airside Business Park Kirkhill Industrial Estate Dyce Aberdeen AB21 0GT UK Tel...

Page 3: ...Issue 2 23 rd June 2011 BA448CF P PROFIBUS PA Intrinsically safe Panel mounting 8 variable Fieldbus Indicator Issue 2...

Page 4: ...ured input parameters 6 4 3 Enter address display parameters 6 4 4 Enable selected input 6 4 5 Enter source address 6 4 6 Enter destination address 6 4 7 Enter Index 6 4 8 Decimal point position 6 4 9...

Page 5: ...es to this manual For additional node configuration information please refer to the BEKA PROFIBUS PA Display Fieldbus Interface Guide which is available from the BEKA sales office or may be downloaded...

Page 6: ...on information The instrument serial number and year of manufacture are shown on the rear panel adjacent to the terminals 4 SYSTEM DESIGN FOR HAZARDOUS AREAS 4 1 FISCO Systems The BA448CF P may be con...

Page 7: ...that even in the event of rare incidents an ignition source due to impact or friction between the aluminium enclosure at the rear of the instrument mounting panel and iron steel is excluded Fig 2 BA4...

Page 8: ...the or button When set as required operating the P button will transfer control to the next digit that may be adjusted in the same way When all digits are set as required operating the E button will...

Page 9: ...BA448CF P listener are not known In the SCAn function pressing the P button causes the BA448CF P listener to search the fieldbus segment to which it is connected for all data sources The hexadecimal...

Page 10: ...8...

Page 11: ...eters Sub menu which allows known fieldbus device addresses to be entered and all display parameters adjusted for each of the eight fieldbus listener inputs See section 6 4 3 Enb Enable selected input...

Page 12: ...source address to the selected input and return the display to the source and destination addresses from which another data source address may be selected When a data source address is allocated to a...

Page 13: ...mode irrespective of the numeric value When positioned as required operating the E button will enter the selection and return to the dP prompt in the edit sub menu 6 4 9 Configuration of bargraph dis...

Page 14: ...evised access code will be activated when the transmitter is returned to the display mode If the access code is lost please contact BEKA associates 6 4 12 Change from fieldbus listener to fieldbus nod...

Page 15: ...y mode 7 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE Live maintenance is permitted on intrinsically safe equipment installed in a hazardous area but only certif...

Page 16: ...a scale for the horizontal bargraph 8 2 Tag number The BA448CF P can be supplied with a thermally printed tag number on the rear panel adjacent to the terminals 8 3 BEKA PROFIBUS PA Display Fieldbus...

Page 17: ...SCO Field Device requirements specified in IEC60079 27 The intrinsically safe system shown in Fig 1 of this manual may therefore be used for installations in the USA and Canada providing the fieldbus...

Page 18: ...16...

Page 19: ...17...

Page 20: ...18...

Page 21: ...19...

Page 22: ...20...

Page 23: ...21...

Page 24: ...22...

Page 25: ...BA448CF P may be installed in Zone 0 explosive gas air mixture continuously present Note Special conditions for safe use apply see above Zone 1 explosive gas air mixture likely to occur in normal oper...