background image

7

6.2.4  Reset the instrument to node factory
          defaults           ‘rESEt’
The  BA448CF-P  may  be  reset  to  the  factory
defaults that are shown below:

Security Code

0000 (disabled)

Device address

126

For each of the eight inputs:

Decimal point

XXX.XX

Bar Type

Left

Bar lower limit

0.0

Bar Upper limit

100.0

Gain

1.0

Offset

0.0

 To  reset  the  BA448CF-P  select  ‘rESEt’  in  the
configuration  menu  by  operating  the 

  or 

button.      To  enter  the  function  press  P  which  will
reveal  ‘0000’  with  the  left  hand  digit  flashing.    To
prevent accidental use of this function, ‘5urE’ must
be  entered  to  confirm  that  the  instrument  is  to  be
reset.

Using the 

 or 

 button set the flashing digit to ‘5’

and press the P button to move control to the next
digit  which  should  be  set  to  ‘u’.    When  the  four
letters of ‘5urE’ have been entered operating the E
button  will  reset  the  BA448CF-P  to  the  factory
defaults.      Any  existing  configuration  and
addresses will be lost when the instrument is reset.

FIG 4 Node configuration menu

6.3  Listener configuration menu
When  used  as  a  fieldbus  listener  the  BA448CF-P
is  not  visible  to  the  fieldbus  host  and  can  only  be
configured  using  the  front  panel  push  buttons
shown in Fig 2.

The  listener  configuration  menu  is  separated  into
three  sections,  ‘SCAn’,  ‘LISt’  and  ‘Edit’,  plus  three
housekeeping functions ‘CodE’, ‘tYPE’ and  ‘rESEt’
as shown in Fig 6.

‘SCAn’  is  the  simplest  method  of  configuration  if
the addresses of the data sources to  be  displayed
by the BA448CF-P listener are not known.

In  the  ‘SCAn’  function  pressing  the  P  button
causes  the  BA448CF-P  listener  to  search  the
fieldbus  segment  to  which  it  is  connected  for  all
data  sources.        The  hexadecimal  device
addresses  for  each  data  source  are  displayed  as
shown in Fig 5.

The 

  and 

  push  buttons  scroll  the  display

through  all  the  data  sources  on  the  segment
showing  the  source  and  destination  address  for
each  one.      To  aid  identification,  operating  the  P
button  will  preview  the  value  of  the  data  at  the
selected  addresses  with  a  zero  index  i.e.  the  first
five  bytes  in  the  data  string.      If  the  format  of  the
data  is  not  DS-33  (status  +  float)  ‘no  dAt’  will  be
displayed.    The  selected  source  and  destination
addresses  may  be  allocated  to  one  of  the  eight
BA448CF-P listener inputs in-1, to in-8.  Operating
the  P  button  will  reveal  the  current  listener  input
which  may  be  changed  using  the 

  or 

  push

button, when set as required, operating the E push
button  will  enter  the  allocation.    If  the  process
variable to be displayed is located further along the
data  stream  i.e.  has  an  index  greater  than  5,  the
required  index  must  be  entered  via  the  index  ‘ind’
function in the edit sub-menu.

A  worked  configuration  example  illustrating  this
procedure is contained in the Quick Set-up section
of  the  BEKA  PROFIBUS  PA  Display  –  Fieldbus
Interface Guide.

Fig 5  Device Addresses

If the source and destination  addresses  and  index
of  the  process  variable  to  be  displayed  by  the
BA448CF-P  listener  are  known,  they  may  be
directly  entered  via  the  edit  sub-menu.    This  sub-
menu also provides full control of both the numeric
and bargraph display parameters.

Summary of Contents for BA448CF-P

Page 1: ...Supplied by Call us on 44 0 118 916 9420 Email info 247able com com Installation Maintenance Instructions BA448CF P...

Page 2: ...Park Danehill Lower Earley Reading Berkshire RG6 4UT UK Tel 44 0 118 9311188 Email info able co uk Aberdeen Office Unit 6 Airside Business Park Kirkhill Industrial Estate Dyce Aberdeen AB21 0GT UK Tel...

Page 3: ...Issue 2 23 rd June 2011 BA448CF P PROFIBUS PA Intrinsically safe Panel mounting 8 variable Fieldbus Indicator Issue 2...

Page 4: ...ured input parameters 6 4 3 Enter address display parameters 6 4 4 Enable selected input 6 4 5 Enter source address 6 4 6 Enter destination address 6 4 7 Enter Index 6 4 8 Decimal point position 6 4 9...

Page 5: ...es to this manual For additional node configuration information please refer to the BEKA PROFIBUS PA Display Fieldbus Interface Guide which is available from the BEKA sales office or may be downloaded...

Page 6: ...on information The instrument serial number and year of manufacture are shown on the rear panel adjacent to the terminals 4 SYSTEM DESIGN FOR HAZARDOUS AREAS 4 1 FISCO Systems The BA448CF P may be con...

Page 7: ...that even in the event of rare incidents an ignition source due to impact or friction between the aluminium enclosure at the rear of the instrument mounting panel and iron steel is excluded Fig 2 BA4...

Page 8: ...the or button When set as required operating the P button will transfer control to the next digit that may be adjusted in the same way When all digits are set as required operating the E button will...

Page 9: ...BA448CF P listener are not known In the SCAn function pressing the P button causes the BA448CF P listener to search the fieldbus segment to which it is connected for all data sources The hexadecimal...

Page 10: ...8...

Page 11: ...eters Sub menu which allows known fieldbus device addresses to be entered and all display parameters adjusted for each of the eight fieldbus listener inputs See section 6 4 3 Enb Enable selected input...

Page 12: ...source address to the selected input and return the display to the source and destination addresses from which another data source address may be selected When a data source address is allocated to a...

Page 13: ...mode irrespective of the numeric value When positioned as required operating the E button will enter the selection and return to the dP prompt in the edit sub menu 6 4 9 Configuration of bargraph dis...

Page 14: ...evised access code will be activated when the transmitter is returned to the display mode If the access code is lost please contact BEKA associates 6 4 12 Change from fieldbus listener to fieldbus nod...

Page 15: ...y mode 7 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE Live maintenance is permitted on intrinsically safe equipment installed in a hazardous area but only certif...

Page 16: ...a scale for the horizontal bargraph 8 2 Tag number The BA448CF P can be supplied with a thermally printed tag number on the rear panel adjacent to the terminals 8 3 BEKA PROFIBUS PA Display Fieldbus...

Page 17: ...SCO Field Device requirements specified in IEC60079 27 The intrinsically safe system shown in Fig 1 of this manual may therefore be used for installations in the USA and Canada providing the fieldbus...

Page 18: ...16...

Page 19: ...17...

Page 20: ...18...

Page 21: ...19...

Page 22: ...20...

Page 23: ...21...

Page 24: ...22...

Page 25: ...BA448CF P may be installed in Zone 0 explosive gas air mixture continuously present Note Special conditions for safe use apply see above Zone 1 explosive gas air mixture likely to occur in normal oper...

Reviews: