background image

5

b.

Fix two panel mounting clips to opposite
sides of the instrument and tighten until the
indicator is secured as shown in Fig 4.

c.

Connect the panel wiring to the rear terminal
block(s) as shown in Fig 3.  To simplify
installation, the terminals are removable so
that the panel wiring can be completed
before the instrument is installed.

Fig 4  Fitting panel mounting clips

4.3  EMC

The BA505C complies with the requirements of
the European EMC Directive.  For specified
immunity all wiring should be in screened twisted
pairs.  The indicator enclosure may be earthed
locally by securing a tag under one of the rear
panel corner fixing screws.

5.  Calibration

The front panel multi-turn control adjusts the set
point station’s output current between
approximately 3.5 and 21mA, no calibration is
required.

5.1  Internal display

The BA505C internal display may be calibrated so
that the 4/20mA loop current is shown in the
required engineering units.

The BA505C display will be supplied calibrated as
requested at time of ordering.   If calibration is not
requested, the display will be set to show 00.0
with 4.000mA loop current, and 100.0 with
20.000mA loop current, but may easily be
recalibrated on-site.

The display is calibrated by plug-in links and two
multi-turn potentiometers that are accessible
through holes in the rear panel.    To gain access
to the links the rear panel must be removed as
shown in Fig 5.

For maximum accuracy the display should be
calibrated using a traceable current measuring
device with an accuracy greater than 4µA.

Fig 5  Removal of rear panel

5.2  Zero adjustment

Zero is defined as the number displayed with a
4.000mA loop current, and may be adjusted
between  -1000 and 1000.   The zero
potentiometer has two ranges, 0 to 500 and 500 to
1000; the polarity of the zero is defined by the
position of the suppression / elevation links.
Fig 6 shows the position of the links and zero
potentiometer.

   

Suppression / elevation links

Elevation

Positive zero

0 to  1000

    or

Suppression

Negative zero

0 to -1000

    

Zero link

0 to 500

    or

500 to 1000

5.3  Span adjustment

Span is defined as the difference between the
number displayed at 4.000mA and the number
displayed at 20.000mA loop current.  The span
potentiometer has four ranges defined by the span
links, and may be adjusted to any number
between 0 and 1999.
Fig 6 shows the position of the links and span
potentiometer.

   

Span links

  000 to   500

    or

  500 to 1000

    or

1000 to 1500

    or

1500 to 1999

Summary of Contents for BA505C

Page 1: ...BA505C 2 wire 4 20mA manual setpoint station Issue 6 Issue 6 3rd December 2010 ...

Page 2: ...Internal display 5 2 Zero adjustment 5 3 Span adjustment 5 4 Decimal point 5 5 Reverse action 5 6 Calibration example 5 7 Over and under range 6 Maintenance 6 1 Fault finding during commissioning 6 2 Fault finding after commissioning 6 3 Servicing 6 4 Guarantee 6 5 Customer comments 7 Accessories 7 1 Scale card 7 2 Tag strip CONTENTS The BA505C is CE marked to show compliance with the European EMC...

Page 3: ...3 5 and 21mA The output resistance of the BA505C is very high so the loop current will be unaffected by changes in supply voltage The 3 digit integral indicator is powered by the 4 20mA loop current and can easily be calibrated on site For example in an application where the BA505C is being used to adjust the set point of a speed controller the internal indicator could be calibrated to display the...

Page 4: ...with and powered by the 4 20mA current from the set point station as shown in Fig 2A This eliminates the need for additional field wiring but the minimum operating voltage of the set point station is increased from 6 1 to 10 0V Fig 2A Application with loop powered backlight 4 Installation 4 1 Location The BA505C is housed in a robust aluminium enclosure with a polyester front panel and a Noryl bez...

Page 5: ... and 100 0 with 20 000mA loop current but may easily be recalibrated on site The display is calibrated by plug in links and two multi turn potentiometers that are accessible through holes in the rear panel To gain access to the links the rear panel must be removed as shown in Fig 5 For maximum accuracy the display should be calibrated using a traceable current measuring device with an accuracy gre...

Page 6: ...n position Step 2 The required zero is 250 therefore the zero link should be put in the 0 to 500 position Step 3 The required span is 900 therefore the span links should be placed in the 500 to 1000 position Step 4 The decimal point is required between the least two significant digits therefore the decimal point link should be placed in the 00 0 position Step 5 Adjust the BA505C front panel contro...

Page 7: ...n functioning correctly the following procedure should be followed Symptom Cause Solution No loop Wiring or Check wiring current power supply and power fault supply Unstable Insufficient Check that loop supply voltage between current voltage terminals 1 3 is between and 6 1 30V Unstable Power supply Reduce ripple display has developed voltage ripple If this procedure does not reveal the cause of t...

Page 8: ... Loosen this screw and carefully pull the control knob from the shaft c Pull the electronic assembly from the rear of the enclosure d Remove the blank scale card and mark with the required legend Replace scale card taking care to align it within the front panel window e Slide the electronic assembly into the rear of the enclosure and guide the control shaft carefully through the front panel seal R...

Reviews: