16
Step 3
Select frequency of max rejection
Scroll though the main menu until
'Cond' is displayed.
Enter the sub-
menu by pressing
P
twice and select
the 'FrE' function.
Using the
Up
or
Down
buttons select '50',
and then
press
E
twice to return to the main
menu.
Step 4
Define function of
P
push-button
Select 'C--P' from the main menu and
press
P
to reveal the function of the
P
button in the display mode. Select '4-
20' and return to the main menu by
pressing
E
.
Step 5
Position dummy decimal point
Select 'd.P' from the main menu and
then press
P
. Using the
Up
and
Down
push-buttons
position
the
dummy
decimal point in front of the least
significant digit.
Press
E
to return to the main menu.
Step 6
Calibrate digital display
With any input current between 4 and
20mA select 'SEt' from the main menu
and press
P.
The indicator will display
'ZErO' in the sub-menu; press
P
to
reveal the existing zero display. Using
the
Up
,
Down
and
P
push-buttons enter
the required zero display of
000.0
Press
E
to return to the 'ZErO' prompt.
Again with any input current between 4
and 20mA press
the Up
push-button
and the indicator will display 'SPAn'.
Press
P
to reveal the existing span
display. Using the
Up
,
Down
and
P
push-buttons enter the required span
display of 1500.0 Press
E
to return to
the 'SPAn' prompt. Press
E
again to
return to the main menu.
The
analogue
bargraph
will
be
automatically calibrated to display 0
with 4mA input and full scale with 20mA
input.
Step 7
Return to display mode
Following completion of calibration
return to the display mode by pressing
'E
'.
7.
MAINTENANCE
7.1
Fault finding during commissioning
If a BA526C fails to function during commissioning
the following procedure should be followed:
Symptom Cause Solution
No display
Incorrect
There should be 1V
wiring
between terminals 1
& 3 with terminal 1
positive.
No display
Incorrect
Check that a current
and no volts wiring or
is flowing in the
between
no power
loop.
terminals
supply.
1 and 3.
Insufficient
Check supply
loop voltage
voltage and
to operate
voltage drops
indicator
caused by all
components in the
loop.
Indicator
Positive
The indicator has
displays 1
over-range
been incorrectly
calibrated & is trying
to display a number
greater than 19999,
or input current is
greater than
approximately 1mA.
Indicator
Negative
The indicator has
displays -1
0ver-range
incorrectly calibrated
& is trying to display
a number less than
-19999, or the input
current is less than
approximately
3.5mA.
Unstable
4/20mA input
Check loop supply
display
has a large
voltage.
ripple content.
Unable to
Incorrect
Enter correct
enter the
security
security code or fit
programme
code
security link in
mode entered.
override
position
See Fig 9.