background image

13

5.5.2

Summary of Timer configuration 
functions

This section summarises all the Timer configuration
functions.   When read in conjunction with Fig 10 it
provides   a   quick   aid   for   configuring   the  Timer.     If
more detail is required, each section of this summary
contains   a   reference   to   a   full   description   of   the
function.

   Display

       Summary of function               

FunCtion

Instrument function

Defines the function of the instrument.
May be set to:

ELAP5E

Timer configuration

CloC

Clock configuration

All  the   entries  in   this  Timer   summary
assume   that   the   BA577E-SS   is
configured   as   a   Timer   by   selecting

ELAP5E

.

See section 5.5.3

inPut

 

Configuration of Input 

Contains   a   sub-menu   with   two   sub-
functions:

inP

 

.

 

tYPE

Selects input sensor type

dEbounCE

Defines input debounce

See section 5.5.4

inP

 

.

 

tYPE

Configures   the   Timer   sensor   input   to
accept one of six types of input:

oP.CoL

Open collector ●

VoLt5  L

Voltage  <1  >3V

VoLt5  H

Voltage  <3  >10V

CoiL

Magnetic pick-off 

Pr.dEt

Proximity detector ●

ContACt

Switch contact ●

● Energise input by linking terminals   

3  & 4.

See section 5.5.5

dEbounCE

Defines the level of debounce applied
to the input to prevent false functioning:

dEFAuLt
HEAVY
LiGHt

See section 5.5.6

   Display

       Summary of function               

di5P-2

Lower display

Configures   the   lower   display   to   show
set   time  

5Et   t

  or,   when   the  

CYCLE5

repeat function is activated, the restart
delay count-down plus the cycle count
number.

With 

CYCLE5

 not enabled:

Select

Lower display shows

  

5td

Set time 

5et t

  

oFF

Disables lower display.

See section 5.5.7

With 

CYCLE5

 enabled:

Select

Lower display shows

  

5td

Cycles requested and  
cycles performed with   
time-down   shown   during  
requested   delay   period.    
Brief   notification   of   timer  
status i.e. 

CYCLE

 or 

dELAY

 at start of each 

period.

  

LAbEL

Exactly as 

5td

 but with 

periodic notification of 
timer   status   i.e.  

CYCLE

  or  

dELAY

.

  

oFF

Disables lower display.

See section 5.5.7

5tAr5toP

Starting and stopping the timer

Defines  how  the Timer is started and
stopped.

Start

  Stop

LoCAL

&

 button

*

 button

ControL 1

Input high

Input low

ControL 2

Input low

Input high

High   and   low   continuous   inputs   are
specified for a voltage input.  For other
types of   sensor input. 

See section 5.5.8

Summary of Contents for BA577E-SS

Page 1: ...Issue 6 4th May 2021 BA577E SS Rugged one input general purpose Timer or Clock Issue 6...

Page 2: ...t 5 5 11 Repeat timing cycle CYCLE5 5 5 12 Cycle function enable EnbL 5 5 13 Cycle count cycl cnt 5 5 14 Restart delay r5t dela 5 5 15 Adjusting the set time 5Et t and restart delay r5t dela from the...

Page 3: ...4 8 Enable Control output 1 EnbL 8 4 9 On and off times oP 1 on 1 oP 1 off 1 oP 1 on 2 oP 1 off 2 8 4 10 Control output 2 Optional oP2 8 4 11 Enable control output 2 EnbL 8 4 12 On and off times oP2...

Page 4: ...circuit that is used for all BA577E SS Timer installations Clock installations are the same except that the input terminals 5 6 are not used For simplicity the optional control outputs are described s...

Page 5: ...etic pick off sensor which is not suitable for controlling the BA577E SS 2 2 5 Voltage input Two voltage input ranges are independently selectable in the BA577E SS Timer configuration menu VoLt5 L and...

Page 6: ...BEKA stainless steel support plate should be slid over the rear of the Counter before the panel clamps are fitted to evenly distribute the clamping force and prevent the enclosure panel being distort...

Page 7: ...g the requested units of measurement if this information is not supplied when the instrument is ordered a blank card will be fitted A pack of self adhesive scale cards printed with common units of flo...

Page 8: ...isplay through which a scale card showing the units of time such as hours can be seen New instruments are fitted with a scale card showing the units of measurement specified when the instrument was or...

Page 9: ...ished via the front panel push buttons or by a remote contact A grand total time is maintained which can be viewed by operating the front panel push buttons It may be reset to zero from within the con...

Page 10: ...5 Shows in succession firmware version number instrument function elap5e and any output accessories that are fitted A Dual Control Outputs Access to configuration menu 5 3 Displays when configured as...

Page 11: ...d of the delay time automatically returns to Running Complete Entered automatically from Running when there are no more timing cycles to perform When the CYCLE5 function is enabled the timing cycle ca...

Page 12: ...he instrument using the or push button to adjust the flashing digit and the push button to transfer control to the next digit If the correct code has been entered pressing will cause the first paramet...

Page 13: ...itch contact Energise input by linking terminals 3 4 See section 5 5 5 dEbounCE Defines the level of debounce applied to the input to prevent false functioning dEFAuLt HEAVY LiGHt See section 5 5 6 Di...

Page 14: ...e display mode to 5Et t and r5t dela See section 5 5 15 Display Summary of function uP or dn Direction of count Defines whether the Timer times down from 5Et t to zero or times up from zero to the set...

Page 15: ...control output 1 See section 5 5 26 Display Summary of function CLr Gtot Resets grand total to zero This function resets the grand total which represents the total Timer run time from within the conf...

Page 16: ...s required press twice to return to the configuration menu or repeatedly press the or button until the required type of input is displayed and then press twice to return to the configuration menu One...

Page 17: ...n at start of each period 02 11 Current Number of cycles cycle requested not shown number when cycle is continuously repeated LabEL Exactly the same as 5td but timer status i e CYCLE or dELAY is shown...

Page 18: ...18...

Page 19: ...19...

Page 20: ...l to the next digit When set as required enter the selection and return to the cycl cnt prompt in the sub menu by operating the button 5 5 14 Restart delay r5t dela This sub function defines the time...

Page 21: ...mediately Continue When power is restored the Timer will continue from where it stopped without any manual intervention To check or change the function select P fail from the configuration menu and pr...

Page 22: ...uration example in section 6 2 of this manual illustrates the use of the control outputs Further examples can be found in Application Guide AG374 which is available on the BEKA website 5 5 22 Control...

Page 23: ...it can be adjusted using the or button and the button to move to the next digit When the required delay has been entered press to return to the control output 1 sub menu The Timer configuration exampl...

Page 24: ...rol to the second digit which should be set to u When 5urE has been entered pressing the button will reset all the configuration functions and return the instrument to the display mode Note r5Et dEF d...

Page 25: ...he required instrument configuration for this example are shown below Function Display Setting Access code CodE 0000 Function FunCtion ELAP5E Input inP type ContACt debounce dEbounCE dEFAuLt Display 2...

Page 26: ...r configuration menu Incorrect security code That the correct security code is being used Contact BEKA if code is lost 7 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTEN...

Page 27: ...e regularly checked Inspection frequency should be chosen to suit the environmental conditions 7 5 Guarantee Instruments which fail within the guarantee period should be returned to BEKA associates or...

Page 28: ...rument s permanent memory Following initialisation the instrument will display a flashing display which is a request for the local time to be entered The clock will not start to function until a displ...

Page 29: ...hroughout this manual push buttons are shown as and and legends displayed by the Clock are shown in a seven segment font as they appear on the instrument e g di5PLAY and CodE Access to the configurati...

Page 30: ...30...

Page 31: ...ntrol output 1 Optional Control output 1 can turn on output closed and off output open twice in each twenty four hour period This function contains five sub function EnbL Enables output 1 and defines...

Page 32: ...et time is entered the Clock will display a flashing 00 00 00 or 00 00 for 24 hour formats or A12 00 00 or A12 00 for 12 hour formats To adjust the clock set time select 5Et from the configuration men...

Page 33: ...tered return to the configuration menu by pressing the button twice 8 4 10 Control output 2 Optional oP2 Control output 2 is an optional factory fitted output which can be configured to turn on output...

Page 34: ...e display mode may be protected by a four digit alphanumeric security code which must be entered to gain access Default security code 0000 allows unrestricted access With ACCd displayed press to enter...

Page 35: ...g will then change the instrument to a Clock and return the display to FunCtion in the configuration menu Step 3 Select display format Using the or button select di5PLAY in the configuration menu and...

Page 36: ...access to the configuration menu Using the and buttons select CodE from the configuration menu and press which will reveal 0000 with the first digit flashing This example requires the security code to...

Page 37: ...ANCE If a BA577E SS fails after it has been functioning correctly as a Clock the following table may help to identify the cause of the failure Symptom Cause Check No display No power supply That there...

Page 38: ...8 10 6 Customer comments BEKA is always pleased to receive comments from customers about our products and services All communications are acknowledged and whenever possible suggestions are implemented...

Reviews: