37
10.
MAINTENANCE when configured as a
Clock
10.1
Fault finding during commissioning
If a BA577E-SS fails to function as a Clock during
commissioning the following procedure should be
followed:
Symptom
Cause
Check:
No display
No power supply, or
incorrect wiring.
Note: Terminals 2 &
RS2 are
interconnected
within the
instrument.
That there is
between 10 and
30V on terminals 1
& 2 with terminal 1
positive.
That there are no
connections to
terminals
3, 4, 5 & 6.
Configuration menu
does not
correspond with the
Clock section of this
manual.
BA577E-SS is
configured as a
Timer.
That
FunCtion
in
configuration menu
is set to
CLoC
not to
ELAP5E
.
Clock display
flashes
00 : 00 : 00
Local time has not
been entered.
Enter the local time
in the
5Et
function
of the instrument
configuration menu.
Control output(s) do
not function.
Control outputs
have not been
enabled.
Enable Control
Output(s) in the
configuration menu.
Clock will not start
Reset terminals
RS1 and RS2 are
connected together
and the clock is
resetting.
If reset annunciator
on the instrument
display is activated,
disconnect link
between RS1 and
RS2.
Unable to enter
configuration menu.
Incorrect security
code
That the correct
security code is
being used.
Contact BEKA if
code is lost.
10.2
Fault finding after commissioning
ENSURE PLANT SAFETY BEFORE
STARTING MAINTENANCE
If a BA577E-SS fails after it has been functioning
correctly as a Clock, the following table may help to
identify the cause of the failure.
Symptom
Cause
Check:
No display
No power supply
That there is
between 10 and
30V on terminals 1
& 2 with terminal 1
positive.
Clock display
flashes
00
:
00
:
00
Instrument power
supply has been
interrupted and
local time has been
lost.
Enter the local time
in the
5Et
function
of the instrument
configuration menu.
Control output(s) do
not function.
Control outputs
have not been
enabled.
Enable Control
Output(s) in the
configuration menu.
Clock will not start
Reset terminals
RS1 and RS2 are
connected together
and the clock is
resetting.
If reset annunciator
on display is
activated,
disconnect
connection between
RS1 and RS2.
Unable to enter
configuration menu.
Incorrect security
code
That the correct
security code is
being used.
Contact BEKA if
code is lost.
If this procedure does not reveal the cause of the
fault, it is recommended that the instrument is
replaced.
10.3
Servicing
We recommend that faulty BA577E-SS Clocks are
returned to BEKA associates or to our local agent for
repair.
10.4
Routine maintenance
The mechanical and electrical condition of the
instrument should be regularly checked. Inspection
frequency should be chosen to suit the
environmental conditions.
10.5
Guarantee
Instruments which fail within the guarantee period
should be returned to BEKA associates or our local
agent. It is helpful if a brief description of the fault
symptoms is provided.
Summary of Contents for BA577E-SS
Page 1: ...Issue 6 4th May 2021 BA577E SS Rugged one input general purpose Timer or Clock Issue 6...
Page 18: ...18...
Page 19: ...19...
Page 30: ...30...