4.  INSTALLATION

4.1 Location
The  BA648CF-F  is  housed  in  a  robust  aluminium
enclosure with a toughened glass window mounted
in  a  Noryl  bezel.    The  front  of  the  instrument
provides  IP66  protection  and  a  gasket  seals  the
joint  between  the  instrument  enclosure  and  the
panel.    The  instrument  may  be  installed  in  any
panel  providing  the  environmental  limits  shown  in
the specification are not exceeded.

Fig  2  shows  the  overall  dimensions  of  the
BA648CF-F and the panel cut-out.  To achieve  an
IP66  seal  between  the  instrument  enclosure  and
the  panel,  the  smaller  cut-out  must  be  used  and
the  instrument  secured  with  four  panel  mounting
clips.

Fig 2  BA648CF-F dimensions

4.2 Installation Procedure

a. Insert  the  BA648CF-F  into  the  instrument

panel cut-out from the front of the panel.

b. Fix panel mounting clips to opposite sides of

the  instrument  and  tighten  until  the
instrument is secure.  Four clips are required
to  achieve  an  IP66  seal  between  the
instrument enclosure and the panel.

c.  Connect  the  panel  wiring  to  the  rear  terminal

block  as  shown  in  Fig  3.      To  simplify
installation,  the  terminals  are  removable  so
that  panel  wiring  can  be  completed  before
the instrument is installed.

Fig 3  Installation and terminal connections

4.3  EMC
The BA648CF-F complies with the requirements of
the  European  EMC  Directive  2004/108/EC.    For
specified  immunity,  all  wiring  should  be  in
screened twisted pairs with the screens earthed at
one point.

Summary of Contents for BA648CF-F

Page 1: ...Issue 3 23 rd June 2011 BA648CF F FOUNDATION fieldbus Panel mounting 8 variable Fieldbus Indicator Issue 3...

Page 2: ...ss display parameters 5 3 6 Enable selected input 5 3 7 Enter Device Address 5 3 8 Enter Variable Identity 5 3 9 Decimal point position 5 3 10 Configuration of bargraph 5 3 11 Scale numeric display 5...

Page 3: ...protocol is shown on the rear of the instrument The F order code suffix also indicates the protocol but is not shown on the instrument idendification label There is an alternative version of the fiel...

Page 4: ...r panel mounting clips Fig 2 BA648CF F dimensions 4 2 Installation Procedure a Insert the BA648CF F into the instrument panel cut out from the front of the panel b Fix panel mounting clips to opposite...

Page 5: ...nditioned as a fieldbus listener see section 5 3 13 to change it to a fieldbus node 5 2 1 Reset the indicator to node factory defaults rESEt The BA648CF F may be reset to the factory defaults that are...

Page 6: ...the P button causes the BA648CF F indicator to search the fieldbus segment to which it is connected for all publishers Fig 5 shows how the indicator displays the hexadecimal Device Address and Variabl...

Page 7: ...vice Address and Variable Identity Parameters can not be changed from within this function See section 5 3 4 Edit Enter addresses and display parameters Contains six sub functions that enable known fi...

Page 8: ...8...

Page 9: ...splayed pressing E will allocate the selected process variable to the selected input and return the display to the Device Address and Variable Identity from which another process variable may be selec...

Page 10: ...function pressing P again will reveal the existing bargraph justification The or button will scroll through the four options when the required justification is displayed pressing E will enter the sele...

Page 11: ...ration menu using the or button To enter the function press P which will show that the instrument is configured as a fieldbus listener to change to a fieldbus node press the or button which will toggl...

Page 12: ...bargraph Bargraph configuration All display segments activated Display is initialising This is normal operation after a few seconds the model number followed by the firmware version will be displayed...

Page 13: ...und the liquid crystal display If specified when the instrument is ordered this can be supplied printed with units of measurement and a scale for the horizontal bargraph 7 2 Tag number The BA648CF F c...

Reviews: