background image

9

5.3.3  Scan fieldbus segment  ‘SCAn’
If  the  Device  Address  and  Variable  Identity  of  a
process  variable  are  not  known,  the  ‘SCAn’
function  provides  a  simple  way  to  identify  them.
This  function  scans  the  fieldbus  segment  to  which
the  BA648CF-F  indicator  is  connected  and
identifies all the publishers.    To  aid  identification  it
enables  the  value  of  each  process  variable  to  be
pre-viewed and, if required, allocated to one of the
eight BA648CF-F Fieldbus indicator inputs.

The  BA648CF-F  indicator  only  supports  DS-65
formatted  data  (float  +  status)  which  is  the  usual
format  for  analogue  process  variables.      The
‘SCAn’  function  will  identify  all  publishers  on  the
segment  irrespective  of  format,  but  when  pre-
viewed,  non  DS-65  formatted  data  will  produce  a
‘no dAt’ error message.

‘SCAn’ is the first function displayed when entering
the  listener  configuration  menu,  or  it  may  be
selected from within the menu by  operating the 

or 

  button.      To  scan  the  fieldbus  segment  to

which  the  indicator  is  connected  for  all  published
data  press  P  which  will  reveal  the  hexadecimal
Device  Address  and  Variable  Identity  of  the  first
publisher  found  as  shown  in  Fig  5.        If  there  is
more  than  one  publisher  operating  the 

  or 

button will scroll though all of them.

If no cyclic  data is being published on the fieldbus
segment  the  BA648CF-F  indicator  will  display
‘noPub’.

When the Device Address and Variable  Identity  of
a  process  variable  is  being  displayed,  pressing  P
will  preview  the  value  of  the  process  variable
displayed with maximum resolution on the five digit
display.      If  this  confirms  that  it  is  one  of  the
process  variables  to  be  displayed,  it  may  be
allocated  to  one  of  the  eight  BA648CF-F  listener
inputs in-1 to in-8.

To  select  the  required  listener  input  press  P  to
display  the  first  input  in-1,  operating  the 

  or 

button  will  scroll  the  display  through  the  other
inputs.    When  the  required  input  is  displayed
pressing  E  will  allocate  the  selected  process
variable to the selected input and return the display
to  the  Device  Address  and  Variable  Identity  from
which another process variable may be selected.

When a process variable is allocated to a indicator
input any previous allocation will be overwritten.

5.3.4 List configured input parameters   ‘LiSt’
The ‘LiSt’ function enables the Device Address and
Variable  Identity  allocated  to  each  lindicator  input
to be viewed without danger of it being accidentally
changed.

The ‘LiSt’ function may be selected from within the
menu  by  operating 

  or 

  button.  To  enter  the

function  press  P  which  will  display  the  indicator
input  currently  selected  in  the  display  mode,  other
inputs  may  be  selected  using  the 

  or 

  button.

Operating  the  P  button  will  cause  the  following
parameters  for  the  selected  input  to  be  displayed
sequentially:

           Display                    Explanation

‘Enb: Y or N’

Input Enabled yes or no

‘Adr:   00’

Device Address

   ‘id:   00’

Variable Identity

The  display  then  automatically  returns  to  the
selected  BA648CF-F  indicator  input  from  where
another input may be selected.

If one of the eight BA648CF-F indicator’s inputs in-
1  to  in-8  has  not  had  a  Device  Address  and
Variable Identity allocated to it, ‘LiSt’ will show both
as invalid address FF.

5.3.5  Enter address & display parameters
          ‘Edit’
The ‘Edit’ function may be selected from within the
menu  by  operating 

  or 

  button.  To  enter  the

function  press  P  which  will  display  the  indicator
input  currently  selected  in  the  display  mode,  other
listener  inputs  may  be  selected  using  the 

  or 

button.    When  the  required  input  has  been
selected  operating  the  P  button  will  enter  the  edit
sub-menu at ‘Enb’ for the selected input.

5.3.6  Enable selected input    ‘Enb’
‘Enb’  turns  the  indicator  input  selected  in  the  Edit
function on or off without affecting the conditioning.
To  enter  the  function  press  P  which  will  reveal
whether  the  selected  input  is  ‘on’  or  ‘oFF’.
Operating the 

 or 

 buttons  will toggle  between

the  two  conditions.    When  set  as  required
operating  the  E  button  will  enter  the  selection  and
return to the edit sub-menu.

Summary of Contents for BA648CF-F

Page 1: ...Issue 3 23 rd June 2011 BA648CF F FOUNDATION fieldbus Panel mounting 8 variable Fieldbus Indicator Issue 3...

Page 2: ...ss display parameters 5 3 6 Enable selected input 5 3 7 Enter Device Address 5 3 8 Enter Variable Identity 5 3 9 Decimal point position 5 3 10 Configuration of bargraph 5 3 11 Scale numeric display 5...

Page 3: ...protocol is shown on the rear of the instrument The F order code suffix also indicates the protocol but is not shown on the instrument idendification label There is an alternative version of the fiel...

Page 4: ...r panel mounting clips Fig 2 BA648CF F dimensions 4 2 Installation Procedure a Insert the BA648CF F into the instrument panel cut out from the front of the panel b Fix panel mounting clips to opposite...

Page 5: ...nditioned as a fieldbus listener see section 5 3 13 to change it to a fieldbus node 5 2 1 Reset the indicator to node factory defaults rESEt The BA648CF F may be reset to the factory defaults that are...

Page 6: ...the P button causes the BA648CF F indicator to search the fieldbus segment to which it is connected for all publishers Fig 5 shows how the indicator displays the hexadecimal Device Address and Variabl...

Page 7: ...vice Address and Variable Identity Parameters can not be changed from within this function See section 5 3 4 Edit Enter addresses and display parameters Contains six sub functions that enable known fi...

Page 8: ...8...

Page 9: ...splayed pressing E will allocate the selected process variable to the selected input and return the display to the Device Address and Variable Identity from which another process variable may be selec...

Page 10: ...function pressing P again will reveal the existing bargraph justification The or button will scroll through the four options when the required justification is displayed pressing E will enter the sele...

Page 11: ...ration menu using the or button To enter the function press P which will show that the instrument is configured as a fieldbus listener to change to a fieldbus node press the or button which will toggl...

Page 12: ...bargraph Bargraph configuration All display segments activated Display is initialising This is normal operation after a few seconds the model number followed by the firmware version will be displayed...

Page 13: ...und the liquid crystal display If specified when the instrument is ordered this can be supplied printed with units of measurement and a scale for the horizontal bargraph 7 2 Tag number The BA648CF F c...

Reviews: