6.  MAINTENANCE

6.1 Fault finding during commissioning
If 

BA648CF-P 

fails 

to 

function 

during

commissioning  the  following  procedure  should  be
followed:

Symptom

Cause

Check:

No Display

Instrument not

correctly

connected or

powered.

9 to 32V between

terminals 1 & 2.

Display shows

‘9.9.9.9.9’ with all

decimal points

flashing; all

bargraph

segments

activated and

bargraph scale

flashing.

Value

over-range

Variable source

Decimal point
configuration.

Display shows

‘-9.9.9.9.9’ with

all decimal points

flashing; no

bargraph

segments

activated and

bargraph scale

flashing.

Value

under-range

Variable source

Decimal point

configuration

Display

alternates

between value

and the word

‘bAd’.  Bargraph

flashes.

Status of fieldbus

variable has a

quality of ‘BAD’

or a fault state is

active.

Display has not

yet received

data.

Variable source

Fieldbus

configuration.

Bargraph scale

flashes.

Variable is

outside the limits

defined for the

bargraph.

Bargraph

configuration.

All display

segments
activated.

Display is

initialising.

This is normal

operation, after a

few seconds the

firmware version
will be displayed

prior to entering

the operational

mode.

6.2  Fault finding after commissioning

ENSURE PLANT SAFETY BEFORE

STARTING MAINTENANCE

If  a  BA648CF-P  fails  after  it  has  been  functioning
correctly,  the  table  shown  in  section  6.1  may  help
to identify the cause of the failure.

If  this  procedure  does  not  reveal  the  cause  of  the
fault,  it  is  recommended  that  the  instrument  is
replaced.

6.3  Servicing
We  recommend  that  faulty  BA648CF-P  Fieldbus
Indicators  be  returned  to  BEKA  associates  or  to
our local agent for repair.

6.4 Routine maintenance
The  mechanical  and  electrical  condition  of  the
instrument  should  be  regularly  checked.    Initially
annual  inspections  are  recommended,  but  the
inspection frequency should be adjusted to suit the
environmental conditions.

6.5  Guarantee
Instruments  which  fail  within  the  guarantee  period
should be returned to BEKA associates or our local
agent.  It is helpful if a brief description of the fault
symptoms is provided.

6.6  Customer comments
BEKA  associates  is  always  pleased  to  receive
comments from customers about our products and
services.    All  communications  are  acknowledged
and 

whenever 

possible, 

suggestions 

are

implemented.

Summary of Contents for BA648CF-P

Page 1: ...Issue 2 23 rd June 2011 BA648CF P PROFIBUS PA Panel mounting 8 variable Fieldbus Indicator Issue 2...

Page 2: ...parameters 5 4 3 Enter address display parameters 5 4 4 Enable selected input 5 4 5 Enter source address 5 4 6 Enter destination address 5 4 7 Enter Index 5 4 8 Decimal point position 5 4 9 Configura...

Page 3: ...n label There is an alternative version of the fieldbus display order code BA648CF F for use on FOUNDATION fieldbus networks 1 1 Documentation This instruction manual describes installation configurat...

Page 4: ...panel mounting clips Fig 2 BA648CF P dimensions 4 2 Installation Procedure a Insert the BA648CF P into the instrument panel cut out from the front of the panel b Fix panel mounting clips to opposite...

Page 5: ...d digit flashing which may be changed by operating the or button When set as required operating the P button will transfer control to the next digit that may be adjusted in the same way When all digit...

Page 6: ...dresses of the data sources to be displayed by the BA648CF P listener are not known In the SCAn function pressing the P button causes the BA648CF P listener to search the fieldbus segment to which it...

Page 7: ...7...

Page 8: ...eters Sub menu which allows known fieldbus device addresses to be entered and all display parameters adjusted for each of the eight fieldbus listener inputs See section 5 4 3 Enb Enable selected input...

Page 9: ...ource address to the selected input and return the display to the source and destination addresses from which another data source address may be selected When a data source address is allocated to a l...

Page 10: ...mode irrespective of the numeric value When positioned as required operating the E button will enter the selection and return to the dP prompt in the edit sub menu 5 4 9 Configuration of bargraph dis...

Page 11: ...evised access code will be activated when the transmitter is returned to the display mode If the access code is lost please contact BEKA associates 5 4 12 Change from fieldbus listener to fieldbus nod...

Page 12: ...ation after a few seconds the firmware version will be displayed prior to entering the operational mode 6 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE If a BA648...

Page 13: ...a scale for the horizontal bargraph 7 2 Tag number The BA648CF P can be supplied with a thermally printed tag number on the rear panel adjacent to the terminals 7 3 BEKA PROFIBUS PA Display Fieldbus...

Reviews: