background image

9

5.4 Description of listener menu functions
This section contains a detailed description of each
function  in  the  listener  configuration  menu.    It
should be read in conjunction with Fig 6.

5.4.1  Scan fieldbus segment  ‘SCAn’
If  the  Device  Addresses  of  a  data  source  are  not
known, the  ‘SCAn’ function provides  a  simple  way
to  identify  them.  This  function  scans  the  fieldbus
segment  to  which  the  BA648CF-P  listener  is
connected  and  identifies  all  the  data  sources.    To
aid  identification  the  value  of  the  process  variable
with a zero index i.e. the first five bytes in the data
string at the address may be pre-viewed.

The  BA648CF-P  listener  only  supports  DS-33
formatted  data  (float)  which  is  the  usual
format  for  analogue  process  variables.      The
‘SCAn’ function  will  identify,  irrespective  of  format,
all data sources on the segment whose destination
address is five bytes long.  When pre-viewed, non
DS-33 formatted data  will  produce  a  ‘no  dAt’  error
message.

‘SCAn’ is the first function displayed when entering
the configuration menu, or it may be selected from
within  the  menu  by  operating  the 

  or 

  button.

To scan the fieldbus segment to which the listener
is connected for all data sources press P which will
reveal  the  hexadecimal  source  address  and
destination  address  of  the  first  data  source  found
as shown in Fig 5.    If there is more than one data
source,  operating  the 

  or 

  button  will  scroll

though all of them.

If  there  are  no  data  sources  on  the  fieldbus
segment  the  BA648CF-P  listener  will  display
‘noSrC’.

When  the  source  and  destination  addresses  of  a
data  source  are  displayed,  to  aid  identification  the
value of the process variable with a zero index i.e.
the  first  five  bytes  in  the  data  string  may  be  pre-
viewed by operating the P button.   If this confirms
that  it  is  the  required  address,  it  may  be  allocated
to one of the eight  BA648CF-P listener  inputs in-1
to in-8.   To select the required listener input, press
P  which  will  display  the  first  input  in-1.    Operating
the 

  or 

  button  will  scroll  the  display  through

the  other  inputs.    When  the  required  input  is
displayed pressing E will allocate the selected data
source address to the selected input and return the
display  to  the  source  and  destination  addresses
from  which  another  data  source  address  may  be
selected.  When a data source address is allocated
to  a  listener  input  any  previous  allocation  will  be
overwritten.

If  the  required  process  variable  has  an  index
above 5  i.e.  it is not the first five bytes in the data
string, the required index should be entered via the
‘ind’  function  in  the  Edit  sub-menu  which  is
described in section 5.4.7

5.4.2 List configured input parameters   ‘LiSt’
The  ‘LiSt’  function  enables  the  Source  Address,
Destination  Address  and  Index  allocated  to  each
listener  input  to  be  viewed  without  danger  of  it
being accidentally changed.

The ‘LiSt’ function may be selected from within the
menu  by  operating 

  or 

  button.  To  enter  the

function press P which will display the listener input
currently selected in the display mode, other inputs
may  be  selected  using  the 

  or 

  button.

Operating  the  P  button  will  cause  the  following
parameters  for  the  selected  input  to  be  displayed
sequentially:

           Display                    Explanation

‘Enb :Y or N’

Input Enabled yes or no

‘SrC :00’

Source Address

‘dSt :00’

Destination Address

‘ind :00’ 

Index

The  display  then  automatically  returns  to  the
selected  BA648CF-P  listener  input  from  where
another input may be selected.

If one of the eight BA648CF-P Listener’s inputs in-
1  to  in-8  has  not  had  a  Source  Address,
Destination Address and Index allocated to it, ‘LiSt’
will  show  both  addresses  as  ‘FF’  and  the  index
‘ind’ as ‘00’.

5.4.3  Enter address & display parameters
          ‘Edit’
The  ‘Edit’  sub-menu  may  be  selected  from  within
the menu by operating 

 or 

 button. To enter the

function press P which will display the listener input
currently  selected  in  the  display  mode,  other
listener  inputs  may  be  selected  using  the 

  or 

button.    When  the  required  input  has  been
selected  operating  the  P  button  will  enter  the  edit
sub-menu at ‘Enb’ for the selected input.

5.4.4  Enable selected input    ‘Enb’
‘Enb’  turns  the  listener  input  selected  in  the  Edit
function on or off without affecting the conditioning.
To  enter  the  function  press  P  which  will  reveal
whether  the  selected  input  is  ‘on’  or  ‘oFF’.
Operating the 

 or 

 buttons  will toggle  between

the  two  conditions.    When  set  as  required
operating  the  E  button  will  enter  the  selection  and
return to the ‘Enb’ prompt in the edit sub-menu.

Summary of Contents for BA648CF-P

Page 1: ...Issue 2 23 rd June 2011 BA648CF P PROFIBUS PA Panel mounting 8 variable Fieldbus Indicator Issue 2...

Page 2: ...parameters 5 4 3 Enter address display parameters 5 4 4 Enable selected input 5 4 5 Enter source address 5 4 6 Enter destination address 5 4 7 Enter Index 5 4 8 Decimal point position 5 4 9 Configura...

Page 3: ...n label There is an alternative version of the fieldbus display order code BA648CF F for use on FOUNDATION fieldbus networks 1 1 Documentation This instruction manual describes installation configurat...

Page 4: ...panel mounting clips Fig 2 BA648CF P dimensions 4 2 Installation Procedure a Insert the BA648CF P into the instrument panel cut out from the front of the panel b Fix panel mounting clips to opposite...

Page 5: ...d digit flashing which may be changed by operating the or button When set as required operating the P button will transfer control to the next digit that may be adjusted in the same way When all digit...

Page 6: ...dresses of the data sources to be displayed by the BA648CF P listener are not known In the SCAn function pressing the P button causes the BA648CF P listener to search the fieldbus segment to which it...

Page 7: ...7...

Page 8: ...eters Sub menu which allows known fieldbus device addresses to be entered and all display parameters adjusted for each of the eight fieldbus listener inputs See section 5 4 3 Enb Enable selected input...

Page 9: ...ource address to the selected input and return the display to the source and destination addresses from which another data source address may be selected When a data source address is allocated to a l...

Page 10: ...mode irrespective of the numeric value When positioned as required operating the E button will enter the selection and return to the dP prompt in the edit sub menu 5 4 9 Configuration of bargraph dis...

Page 11: ...evised access code will be activated when the transmitter is returned to the display mode If the access code is lost please contact BEKA associates 5 4 12 Change from fieldbus listener to fieldbus nod...

Page 12: ...ation after a few seconds the firmware version will be displayed prior to entering the operational mode 6 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE If a BA648...

Page 13: ...a scale for the horizontal bargraph 7 2 Tag number The BA648CF P can be supplied with a thermally printed tag number on the rear panel adjacent to the terminals 7 3 BEKA PROFIBUS PA Display Fieldbus...

Reviews: