Wrong
Right
Description / explanation
Manifold design
• The cross-section of the manifold must be at
least equal to the sum of the individual cross-
sections of the connected feed lines.
• Lay the manifold with a continuous slope
> 3 %.
Diameters of the connected lines
• The minimum diameters of the feed line and
the drain line
must be at least 1/2" (interior
diameter at least 13 mm (0.5 in)).
•
Do not fit any reductions in the line (e.g. using
reducing nipples or fittings).
Bypassing filters
• Drain each condensate collection point with a
separate
BEKOMAT
®
.
•
Do not create any filter bypass points.
Ensure venting
•
If the slope in the inflow is not sufficient or
there are other problems with the inflow,
install a venting line.
0
Connect the feed line to the condensate
inlet
[E]
.
0
Connect the venting line to the
condensate inlet
[C]
.
BEKOMAT
®
33iU / 33iU CO
Original installation and operation manual
30 | 68