Split-type room air conditioner / Installation Manual
23 / 120 EN
Minimum cross-sectional area of power and signal cables
North America
Appliance Amps (A)
COOL mode
10
18
13
16
18
14
25
12
30
10
Other regions
Rated current of appliance (A)
Nominal cross-sectional area
(mm²)
> 3 and ≤ 6
0.75
> 6 and ≤ 10
1
> 10 and ≤ 16
1.5
> 16 and ≤ 25
2.5
> 25 and ≤ 32
4
> 32 and ≤ 40
6
Choose the right cable size
The size of the power supply cable, signal cable, fuse, and switch needed is determined by the
maximum current of the unit. The maximum current is indicated on the nameplate located on the side
panel of the unit. Refer to this nameplate to choose the right cable, fuse, or switch.
Take note of fuse specifications
The air conditioner’s circuit board (PCB) is designed with a fuse to provide overcurrent protection. The
specifications of the fuse are printed on the circuit board, such as: T3.15A/250VAC, T5A/250VAC, etc.
Indoor unit:
T5A/250VAC
Outdoor unit
(applicable to units adpot R32 or R290 refrigerant only):
T20A/250VAC (<=18000Btu/h units)
T30A/250VAC (>18000Btu/h units)
C
Note:
The fuse is made of ceramic.
5
Indoor unit installation
Summary of Contents for BEVPI 090
Page 118: ......
Page 119: ......
Page 120: ...www beko com ...
Page 121: ...Air conditioner remote control User Manual EN ...
Page 128: ...8 24 EN Air conditioner remote control User Manual 3 Handling the remote control ...
Page 142: ......
Page 143: ......
Page 144: ...www beko com ...
Page 145: ......
Page 166: ......
Page 167: ......
Page 168: ...www beko com ...