Split-type room air conditioner / Installation Manual
47 / 120 EN
Additional refrigerant per pipe length
Connective pipe
length (m)
Air purging
method
Additional refrigerant
≤ Standard pipe
length
Vacuum
Pump
N/A
> Standard pipe
length
Vacuum
Pump
Liquid Side: Ø 6.35 (ø 0.25”)
R22:
(Pipe length – standard length) x 30g/m
(Pipe length – standard length) x 0.32oZ/ft
Inverter R410A:
(Pipe length – standard length) x 15g/m
(Pipe length – standard length) x 0.16oZ/ft
Fixed-frequency R410A:
(Pipe length – standard length) x 20g/m
(Pipe length – standard length) x 0.21oZ/ft
Liquid Side: Ø 9.52 (ø 0.375”)
R22:
(Pipe length – standard length) x 60g/m
(Pipe length – standard length) x 0.64oZ/ft
Inverter R410A:
(Pipe length – standard length) x 30g/m
(Pipe length – standard length) x 0.32oZ/ft
Fixed-frequency R410A:
(Pipe length – standard length) x 40g/m
(Pipe length – standard length) x 0.42oZ/ft
A
Warning
DO NOT mix refrigerant types.
8