9.3
Start-up and shut down
Start-up (refer to paragraph 11.1 Control Panel)
•
Check the condenser for cleanliness.
•
Verify that the system is powered.
•
Activate the main switch - pos. 1 on the control panel.
•
Ensure that electronic controller DMC14 is ON.
•
Wait a few minutes; verify that the DewPoint temperature displayed on electronic instrument DMC14 is correct and
that the condensate is regularly drained.
•
Switch on the air compressor.
Shut down (refer to paragraph 11.1 Control Panel)
•
Verify that the DewPoint temperature displayed on electronic controller DMC14 is correct.
•
Switch OFF the air compressor.
•
After a few minutes, switch off the main switch on the control panel of the dryer (pos. 1).
NOTE : A DewPoint within 32°F (0°C) and +60°F (15°C) displayed on DMC14 is correct according to the possible
working conditions (flow-rate, temperature of the incoming air, ambient temperature, etc.).
During the operation, the refrigerating compressor will run continuously. The dryer must remain on during the full usage
period of the compressed air, even if the air compressor works intermittently.
The
number of starts must be no more than 6 per hour.
The dryer must stop running for at least 5 minutes
before being started up again.
The user is responsible for compliance with these rules. Frequent starts may cause irreparable damage.
Summary of Contents for DRYPOINT RA HT 100-P NA UL
Page 19: ...DRYPOINT RA HT 20 350 NA UL 19 10 2 Technical data DRYPOINT RA HT 150 350 NA E 1 230 60 UL ...
Page 34: ...Appendices 34 DRYPOINT RA HT 20 350 NA UL 13 1 2 Dryers Dimensions DRYPOINT RA HT 75 NA UL ...
Page 35: ...Appendices DRYPOINT RA HT 20 350 NA UL 35 13 1 3 Dryer dimensions DRYPOINT RA HT 100 NA UL ...
Page 36: ...Appendices 36 DRYPOINT RA HT 20 350 NA UL 13 1 4 Dryer dimensions DRYPOINT RA HT 150 NA UL ...
Page 46: ...Appendices 46 DRYPOINT RA HT 20 350 NA UL 13 3 2 Electric diagram DRYPOINT RA HT 20 50 NA UL ...
Page 47: ...Appendices DRYPOINT RA HT 20 350 NA UL 47 13 3 3 Electric diagram DRYPOINT RA HT 75 100 NA UL ...
Page 48: ...Appendices 48 DRYPOINT RA HT 20 350 NA UL 13 3 4 Electric diagram DRYPOINT RA HT 150 NA UL ...
Page 51: ...Appendices ...