Start-up
18
DRYPOINT® RS 15-550 HP50 NA
9.3
Shut down and restart
RS 180-550 3phase - during short-term inactivity (max. two to three days), it is advisable to leave the dryer
and the control panel connected to the supply current circuit. Otherwise, it would be necessary at a restart
of the dryer to wait two hours, until the crankcase heater of the compressor has heated up the oil in the
compressor.
Shut down (see Section 11.1 "Control panel")
• Ensure that the dew point temperature indicated on the electronic control unit is stable.
• Interrupt the compressed-air supply.
• After a few minutes, stop the dryer by switching off the main switch on the control panel (pos. 1).
Restart (see Section 11.1 "Control panel"
)
• Make sure that the condenser is clean (air-cooled).
• Ensure that the cooling-water flow and the temperature are in accordance with the provisions (water-cooled).
• Check whether or not voltage is applied at the dryer.
• Start the dryer by switching on the main switch on the control panel (pos. 1).
• Ensure that the electronic control unit is switched on.
• Wait a few minutes and then check, whether or not the dew point temperature indicated on the
electronic control unit is stable and whether or not the condensate is drained off at regular intervals.
• Establish the compressed-air supply.
RS 180-550 3phase - dryer remote control ON/OFF
• Remove the jumper between terminals 1 and 2 of the terminal strip and wire a potential-free contact (see electric
diagram).
• Switch ON the main switch - pos. 1 on the control panel.
• Close the contact at terminals 1 and 2 to switch on the dryer.
• Open the contact at terminals 1 and 2 to switch off the dryer.
Only use potential-free contacts that are suitable for low voltage. Ensure the sufficient insulation of
potentially dangerous voltage-carrying components.
Caution!
Automatic restart / remote control ON/OFF. The unit may start up without any active influence!
The user will be responsible for the installation of proper protections for possible sudden power
restoration to the dryer.
During the operation, the refrigerating compressor runs continuously. The dryer needs to be switched on during the
entire compressed-air usage time, even if the compressed-air compressor works periodically.
Note!
RS 15-40 - A dew point included in the green operating area of the electronic control unit is considered to
be correct according to the possible operating conditions (flow rate, air inlet temperature, ambient
temperature etc.).
RS 50-550 - A dew point between 32°F (0°C) and +50°F (+10°C) displayed on the electronic control unit is
considered to be correct according to the possible operating conditions (flow rate, air inlet temperature,
ambient temperature etc.).
Note!
The dryer
must not be started up more than six times an hour
. Wait at least five minutes prior to every
restart. The user is responsible for the compliance with these provisions. Irreparable damage can be
caused when starting up the device too often.
Summary of Contents for DRYPOINT RS 100-E HP50 NA
Page 22: ...22 DRYPOINT RS 15 550 HP50 NA 10 4 Technical data DRYPOINT RS 180 550 3phase HP50 NA 3 380 60 ...
Page 40: ...Appendices 40 DRYPOINT RS 15 550 HP50 NA 13 1 2 Dryer dimensions DRYPOINT RS 50 80 HP50 NA ...
Page 41: ...Appendices DRYPOINT RS 15 550 HP50 NA 41 13 1 3 Dryer dimensions DRYPOINT RS 100 140 HP50 NA ...
Page 42: ...Appendices 42 DRYPOINT RS 15 550 HP50 NA 13 1 4 Dryer dimensions DRYPOINT RS 180 350 HP50 NA ...
Page 43: ...Appendices DRYPOINT RS 15 550 HP50 NA 43 13 1 5 Dryer dimensions DRYPOINT RS 450 550 HP50 NA ...
Page 47: ...Appendices DRYPOINT RS 15 550 HP50 NA 47 13 2 2 Exploded diagram DRYPOINT RS 15 40 HP50 NA ...
Page 48: ...Appendices 48 DRYPOINT RS 15 550 HP50 NA 13 2 3 Exploded diagram DRYPOINT RS 50 80 HP50 NA ...
Page 49: ...Appendices DRYPOINT RS 15 550 HP50 NA 49 13 2 4 Exploded diagram DRYPOINT RS 100 140 HP50 NA ...
Page 59: ...Appendices DRYPOINT RS 15 550 HP50 NA 59 13 3 2 Electric diagram DRYPOINT RS 15 40 HP50 NA ...
Page 60: ...Appendices 60 DRYPOINT RS 15 550 HP50 NA 13 3 3 Electric diagram DRYPOINT RS 50 80 HP50 NA ...
Page 61: ...Appendices DRYPOINT RS 15 550 HP50 NA 61 13 3 4 Electric diagram DRYPOINT RS 100 140 HP50 NA ...
Page 62: ...Appendices 62 DRYPOINT RS 15 550 HP50 NA 13 3 5 Electric diagram DRYPOINT RS 180 260 HP50 NA ...
Page 63: ...Appendices DRYPOINT RS 15 550 HP50 NA 63 13 3 6 Electric diagram DRYPOINT RS 350 HP50 NA ...
Page 64: ...Appendices 64 DRYPOINT RS 15 550 HP50 NA 13 3 7 Electric diagram DRYPOINT RS 450 550 HP50 NA ...
Page 71: ...DRYPOINT RS 15 550 HP50 NA 71 ...