Technical description
DRYPOINT® RS 15-550 HP50 NA
29
11.19 Electronic controller DMC34
Led - Temperature in °C
Led - Temperature in °F
Led
– Drain ON
Led
– Fan ON
Led
– Alarm/Service
Button
– Setup menu access /
Condensing
Button
– Decrease / Service
Button
– Increase / Drain test
The DMC34 displays DewPoint temperature, controls the condenser fan activation, handles a service reminder and keep
record of the total hours of operation of the dryer.
11.19.1 How to switch on the dryer
Power the dryer and switch it on using the ON-OFF switch (pos. 1 paragraph 11.1).
During normal operation the display shows the DewPoint temperature.
The condensate drain test is always active using the button
.
11.19.2 How to switch off the dryer
Switch it off using the ON-OFF switch (pos. 1 paragraph 11.1).
11.19.3 How to display the operating parameters
During normal operation, the display shows the DewPoint temperature (in °C or °F).
Press and hold
button to display condensing pressure.
Press and hold
button to display hours until the next service.
Press and hold
+
buttons to display total hours of operation of the dryer (cannot be reset).
NOTE :
with led
on temperatures are in °C and pressure in barg; with led
on temperatures are in °F and
pressure in psig.
The total hours of operation and the hours until th
e next service are shown in the field 0…999 hours and
in thousands of hours from 01.0 hours on (example : if the display shows number 35 it means 35 hours; if
the display shows number 3.5 it means 3500 hours).
11.19.4 How a service warning / alarm is displayed
A service warning / alarm is an unusual event that must recall the attention of the operators/maintenance technicians. It
does not stop the dryer.
When a service warning / alarm is active, the
led is lighted or flashing.
Service warnings / alarms are automatically reset as soon as the problem is solved and dryer is powered again.
Scheduled Service reminder requires manual reset.
NOTE: the operator/maintenance technician must inspect the dryer and verify/solve the problem that generated
the service warning.
Service Warning / Alarm
Description
fl
on display
PF1 - Probe 1 Failure : failure temperature probe BT1
fl
on display
PF2 - Probe 2 Failure : failure pressure probe BP2
fl
on display
HdP - High DewPoint: DewPoint too high
Set BT1>HdS, delay Hdd / Reset BT1<HdS-1°C (HdS-2°F)
fl
on display
LdP - Low DewPoint : DewPoint too low
Set BT1< -1°C (30°F), delay 5 minutes / Reset T1> 1°C (34°F)
fl
on display
SrV - Service : maintenance service time expired SrV
Set
PQ
S008
4
DISPLAY
Set
Set
Set
Summary of Contents for DRYPOINT RS 100-E HP50 NA
Page 22: ...22 DRYPOINT RS 15 550 HP50 NA 10 4 Technical data DRYPOINT RS 180 550 3phase HP50 NA 3 380 60 ...
Page 40: ...Appendices 40 DRYPOINT RS 15 550 HP50 NA 13 1 2 Dryer dimensions DRYPOINT RS 50 80 HP50 NA ...
Page 41: ...Appendices DRYPOINT RS 15 550 HP50 NA 41 13 1 3 Dryer dimensions DRYPOINT RS 100 140 HP50 NA ...
Page 42: ...Appendices 42 DRYPOINT RS 15 550 HP50 NA 13 1 4 Dryer dimensions DRYPOINT RS 180 350 HP50 NA ...
Page 43: ...Appendices DRYPOINT RS 15 550 HP50 NA 43 13 1 5 Dryer dimensions DRYPOINT RS 450 550 HP50 NA ...
Page 47: ...Appendices DRYPOINT RS 15 550 HP50 NA 47 13 2 2 Exploded diagram DRYPOINT RS 15 40 HP50 NA ...
Page 48: ...Appendices 48 DRYPOINT RS 15 550 HP50 NA 13 2 3 Exploded diagram DRYPOINT RS 50 80 HP50 NA ...
Page 49: ...Appendices DRYPOINT RS 15 550 HP50 NA 49 13 2 4 Exploded diagram DRYPOINT RS 100 140 HP50 NA ...
Page 59: ...Appendices DRYPOINT RS 15 550 HP50 NA 59 13 3 2 Electric diagram DRYPOINT RS 15 40 HP50 NA ...
Page 60: ...Appendices 60 DRYPOINT RS 15 550 HP50 NA 13 3 3 Electric diagram DRYPOINT RS 50 80 HP50 NA ...
Page 61: ...Appendices DRYPOINT RS 15 550 HP50 NA 61 13 3 4 Electric diagram DRYPOINT RS 100 140 HP50 NA ...
Page 62: ...Appendices 62 DRYPOINT RS 15 550 HP50 NA 13 3 5 Electric diagram DRYPOINT RS 180 260 HP50 NA ...
Page 63: ...Appendices DRYPOINT RS 15 550 HP50 NA 63 13 3 6 Electric diagram DRYPOINT RS 350 HP50 NA ...
Page 64: ...Appendices 64 DRYPOINT RS 15 550 HP50 NA 13 3 7 Electric diagram DRYPOINT RS 450 550 HP50 NA ...
Page 71: ...DRYPOINT RS 15 550 HP50 NA 71 ...