Operation
METPOINT
®
OCV
61
For the transmission of the 4-20 mA signal, a two-pole M16 cable connector can be connected at position (1) at the
evaluation unit.
Cable connector with screen ring
Two-pole
M 16
Cable bushing 4-6 mm
Available as accessories.
Order number 4014143
CAUTION!
The 4….20 mA interface is designed as an
active current source
and is galvanically separated
from the rest of the circuit by a 1 kV isolation barrier. The current to be measured depends on the
connected load.
Only a passive current sink is to be connected to the 4….20 mA interface. For correct
functioning, the connected load must lie within a range between 0 and max. 500 Ohm.