OPERATING MODE

 

UPS MODE 

 

UPS Mode: 

In UPS mode the LDD960-UU protects a load from unwanted power interruption in 
case of mains failure. An example of UPS connection is given on to the side. When 
the input is present LDD960-UU acts as a bypass, connecting the input to the output 
via the input switch. Meanwhile, if required, the battery is charged. During bypass 
there is no voltage conversion, therefore the output supply voltage is equal to the 
input voltage. 
In case of power outage, the LDD960-UU takes energy from the battery to keep the 

output regulated at “

Nominal output voltage

”.

 

 
Backup: 

The system is in backup mode if the supply for the output is sourced from the battery 
(input supply missing). During backup the battery is monitored continuously to 
prevent over discharge. 
A programmable backup timer is also implemented in order to fix a maximum backup 
time during power outages. This allows preserving the battery life and shortening the 
recharge time, avoiding discharging the battery when not needed. During backup the 
internal Coulomb counter is used to give an estimate of the residual charge of the 
battery. 

Backup starts when the output voltage is lower than 90% of the “

Nominal output 

voltage

”.

 

 
Battery charger: 

The battery charger supports various chemistries such Lead-Acid, Nickel, Lithium and 
Super-capacitors. Other charging algorithms can be implemented by request (contact 
factory). 
The battery charger automatically reduces the current to avoid exceeding the 
maximum input current in case of high current load. 

Warnings:

 

-

 

In order to avoid potentially hazardous situations including fire hazard, safety recommendations must be followed. Only authorized staff can install 
the unit. 

-

 

For Lithium cells the balancing and protection circuit must be included in the battery pack. 

-

 

For Nickel batteries the use of the external temperature sensor is mandatory. The sensor must be placed in contact with the battery. 

 

 

DC-DC MODE 

 

DC-DC Mode:

 

LDD960-UU can be used as a high performance DC/DC converter.  
An example of DC/DC connection is given on to the side. 

Any voltage between 10 V to 55 V can be converted to any voltage between 10 V to 
55 V (step-up and step-down operation) with up to 20A input or output current. 

Input and output are protected against over current with user settable limits. When 
used as a DC/DC converter the input supply must be connected to the battery 
connector as shown on to the side. 

 
 
 
 

 

Summary of Contents for LDD960-UU

Page 1: ...y out work on live parts Danger of fatal injury The product s enclosure may be hot allow time for cooling product before touching it Do not allow liquids or foreign objects to enter into the products To avoid sparks do not connect or disconnect the device before having previously turned off input power and wait for internal capacitors discharge minimum 1 minute GEFAHR VON VERBRENNUNGEN EXPLOSIONEN...

Page 2: ... connected to the load to be backed up 10 Battery connection 2 poles are provided for battery connection This must be connected to the battery Please respect the correct polarity 11 Display area provides information regarding the device status 12 Control keys 4 push buttons are provided to navigate through the menus and to select the various functions USER INTERFACE SYMBOL NAME FUNCTION MENU KEY S...

Page 3: ...ckup the internal Coulomb counter is used to give an estimate of the residual charge of the battery Backup starts when the output voltage is lower than 90 of the Nominal output voltage Battery charger The battery charger supports various chemistries such Lead Acid Nickel Lithium and Super capacitors Other charging algorithms can be implemented by request contact factory The battery charger automat...

Page 4: ...ltaneously the buttons until you see the welcome message on the screen On the status screen the Cold start text is written beside the input icon Release the buttons PC shutdown and automatic restart PC shutdown In case the LDD960 UU is used to supply a PC it is possible to automatically shut down the PC after an adjustable time of backup For this the PC must run the POWERMASTER application provide...

Page 5: ...y SoC 25 Bat SoC 25 Active when the battery State of Charge is under 25 of the nominal full charge capacity Battery over discharge current Bat over dis I Active when the measured battery discharge current reaches the threshold specified in Battery max discharge current field Battery low Bat low Active when the measured battery voltage is under the threshold specified in Battery low voltage field B...

Page 6: ...wer side with suitable cooling and maintaining a proper distance between adjacent devices as specified in the Installation Instruction of each family MOUNTING 1 Tilt the unit slightly backwards 2 Fit the unit over the top edge of the rail 3 Slide it downward until it hits the stop 4 Press against the bottom for locking 1 2 3 4 DISMOUNTING 1 Pull down the slide clamp lever 2 Tilt the unit upward 3 ...

Reviews: