FIG.1 - CONNECTIONS 

FIG.2 - DIMENSIONS 

FIG.3 - DISTANCES 

 

Just for reference 

(1)

 

AC/DC input 

(2)

 

DC output (load) 

(3)

 

Diagnostic Output  
(dry contact, NC output OK) 

(4)

 

Green LED: Output OK 

(5)

 

Output voltage adjustment 

 

Input AC Line: 

 

L = Line 

 

N = Neutral 

 

= Earth ground 

 

Input DC Line: 

 

L = + Positive DC 

 

N = - Negative DC 

 

= Earth ground 

 

Output: 

 

+ = Positive DC 

 

- = Negative DC 

 

Dry contact = NC 

 

 

 

 

Dimension 


mm (inc) 

40 (1.57) 

110 (4.33) 
115 (4.52) 

Distance 


mm (inc) 

20 (0.8) 
50 (2.0) 

 
 

FIG.4 - MOUNTING / DISMOUNTING INSTRUCTIONS 

 
For DIN rail fastening according to IEC 60715 TH35-7.5(-15) 
Mounting as shown in figure, with input terminals on lower side, with suitable cooling and maintaining a proper distance between adjacent devices as specified in the 
Installation Instruction of each family. 

 

MOUNTING: 

 

1.

 

Tilt the unit slightly backwards. 

2.

 

Fit the unit over the top edge of the rail. 

3.

 

Slide it downward until it hits the stop. 

4.

 

Press against the bottom for locking. 

 

 

 

 

DISMOUNTING: 

 

1.

 

Pull down the slide clamp lever 

2.

 

Tilt the unit upward 

3.

 

Unhook the unit from the rail

 

 

 

1 & 2 

 

 

 
 
 

Summary of Contents for LDN85 Series

Page 1: ...ts To avoid sparks do not connect or disconnect the device before having previously turned off input power and wait for internal capacitors discharge minimum 1 minute GEFAHR VON VERBRENNUNGEN EXPLOSIONEN FEUER STROMSCHLAG PERSONENSCHÄDEN Führen Sie niemals Arbeiten an spannungsführenden Teilen durch Gefahr von tödlichen Verletzungen Das Gehäuse des Gerätes kann heiß sein lassen Sie Zeit zum Abkühl...

Page 2: ...itive pole N terminal to negative pole and terminal to GND Rated voltage 110 345 VDC The device is also suitable for photovoltaic or wind turbine applications see Fig 7 7 OUTPUT CONNECTION The device is suitable for SELV and PELV circuitry Vout can be adjusted with a potentiometer to a wide range see Fig 1 Check Vout before connecting the power supply to the load With output voltage set to the max...

Page 3: ... 52 Distance A B mm inc 20 0 8 50 2 0 FIG 4 MOUNTING DISMOUNTING INSTRUCTIONS For DIN rail fastening according to IEC 60715 TH35 7 5 15 Mounting as shown in figure with input terminals on lower side with suitable cooling and maintaining a proper distance between adjacent devices as specified in the Installation Instruction of each family MOUNTING 1 Tilt the unit slightly backwards 2 Fit the unit o...

Page 4: ...alent type Surge protection it is strongly recommended to provide external surge arresters SPD according to local regulations FIG 7 INPUT CONNECTIONS AC LINE DC LINE FIG 8 ENVIRONMENT OPERATING TEMPERATURE DERATING 40 C to 70 C 5 95 r H non condensing UL Certified up to 60 C No derating NOTES Data may change without prior notice in order to improve the product Please refer to the latest version of...

Reviews: