INSTALLATION INSTRUCTION 

 

 

Manufacturer 

Bel Fuse Inc. 

206 Van Vorst St. 

Jersey City  

NJ 07302, USA 

Asia-Pacific 

+86 755 2988 5888

 

Europe, Middle East 

+353 61 225 977

 

North America 

+1

 

408

 

785 5200

 

© 2021 Bel Power Solutions & Protection

 

BCM.00441_AD

 

 

 

 

FIG.5 - RECOMMENDED CONNECTING CABLE 

 

Recommended Tightening torque 

0.5 - 0.6 Nm 
4.42 - 5.30 lbf in 

 

 

 

Solid: 2.5 mm² / 12 AWG 
Stranded:1.5 mm² / 12 AWG 
L: 6.0 - 7.5 mm / 0.24 - 0.30 in 

 
 

FIG.6 - INPUT PROTECTION 

Fuse 6AT or MCB 6 A C curve. 
For USA and Canada, use the fuse type closest to the European equivalent type. 
 

Surge protection: 

it is strongly recommended to provide external surge arresters (SPD) according to local regulations. 

 
 

FIG.7 - INPUT CONNECTIONS 

AC LINE 

DC LINE 

 

 

 

 

FIG.8 - ENVIRONMENT 

OPERATING TEMPERATURE 

DERATING 

- 40°C to + 70°C 
5 - 95% r.H. non condensing 
UL Certified up to 60°C 

No derating 

 

 

NOTES:

 

 

 

Data may change without prior notice in order to improve the product. 

 

Please refer to the latest version of the Installation Instruction for each product by visiting

 

belfuse.com/power-solutions

 

 
 

ACCESSORIES

 

 

LDX-D20 

20 A Active ORing controller 

 

LDX-D50        50 A Active ORing controller 

 

LDX-U20 

20 A High performance DC UPS 

 

LDX-B20 

150J Buffer Module 

 

LDX-C120 

Battery charger and DC UPS Module 

 

LDX-L30 

Sealed Lead acid Battery pack 

 
 

 

Summary of Contents for LDN85 Series

Page 1: ...ts To avoid sparks do not connect or disconnect the device before having previously turned off input power and wait for internal capacitors discharge minimum 1 minute GEFAHR VON VERBRENNUNGEN EXPLOSIONEN FEUER STROMSCHLAG PERSONENSCHÄDEN Führen Sie niemals Arbeiten an spannungsführenden Teilen durch Gefahr von tödlichen Verletzungen Das Gehäuse des Gerätes kann heiß sein lassen Sie Zeit zum Abkühl...

Page 2: ...itive pole N terminal to negative pole and terminal to GND Rated voltage 110 345 VDC The device is also suitable for photovoltaic or wind turbine applications see Fig 7 7 OUTPUT CONNECTION The device is suitable for SELV and PELV circuitry Vout can be adjusted with a potentiometer to a wide range see Fig 1 Check Vout before connecting the power supply to the load With output voltage set to the max...

Page 3: ... 52 Distance A B mm inc 20 0 8 50 2 0 FIG 4 MOUNTING DISMOUNTING INSTRUCTIONS For DIN rail fastening according to IEC 60715 TH35 7 5 15 Mounting as shown in figure with input terminals on lower side with suitable cooling and maintaining a proper distance between adjacent devices as specified in the Installation Instruction of each family MOUNTING 1 Tilt the unit slightly backwards 2 Fit the unit o...

Page 4: ...alent type Surge protection it is strongly recommended to provide external surge arresters SPD according to local regulations FIG 7 INPUT CONNECTIONS AC LINE DC LINE FIG 8 ENVIRONMENT OPERATING TEMPERATURE DERATING 40 C to 70 C 5 95 r H non condensing UL Certified up to 60 C No derating NOTES Data may change without prior notice in order to improve the product Please refer to the latest version of...

Reviews: