background image

5

 

INSTALLATION INSTRUCTION 

 

 

Asia-Pacific 

+86 755 298 85888

 

Europe, Middle East 

+353 61 225 977

 

North America 

+1

 

408

 

785 5200

 

© 2020 Bel Power Solutions & Protection

 

BCM.00439_AC

 

 

FIG.7 - INPUT CONNECTIONS 

AC LINE 

 SINGLE PHASE 

AC LINE 

 TWO PHASES 

 

 

DC LINE 

 

 

 

 

 

FIG.8 - ENVIRONMENT 

OPERATING TEMPERATURE 

DERATING 

- 40°C to + 70°C 
5 - 95% r.H. non condensing 
 

- 4.2 W / °C over 50°C 
Do not exceed Vout x Iout = 100 W Max at 70°C 

 

 

NOTES:

 

 

 

Data may change without prior notice in order to improve the product. 

 

Please refer to the latest version of the Installation Instruction for each product by visiting

 

belfuse.com/power-solutions

 

 

 

ACCESSORIES

 

 

LDX-D20 

20 A Active ORing controller 

 

LDX-D50        50 A Active ORing controller 

 

LDX-B20 

150J Buffer Module 

 

Summary of Contents for LDP200-200

Page 1: ...ing previously turned off input power and wait for internal capacitors discharge minimum 1 minute GEFAHR VON VERBRENNUNGEN EXPLOSIONEN FEUER STROMSCHLAG PERSONENSCHÄDEN Führen Sie niemals Arbeiten an spannungsführenden Teilen durch Gefahr von tödlichen Verletzungen Das Gehäuse des Gerätes kann heiß sein lassen Sie Zeit zum Abkühlen des Gerätes bevor Sie es berühren Lassen Sie keine Flüssigkeiten o...

Page 2: ...s see Fig 7 7 ENABLE INPUT CONNECTION The device can be connected to AC lines or DC lines to provide an enable signal With DC lines please be sure to respect the polarity Rated voltage 12 230 VAC VDC The ENABLE line should be provided with a fuse type T rated 250 V 100 mA The ENABLE signal allows the output voltage to be switched ON or OFF The ENABLE signal operating modes can be configured in the...

Page 3: ...and U2 U1 dEL Configuration Delay Time Settable 0 0 99 9 s U2 Configuration second output voltage Settable 36 205 VDC Errors Displayed OFF Output inactive En Enable is active En 1 and the enable input is not active OL Output switched off because the Output voltage below 30 VDC 3 s No auto recovery recovery by primary shutdown or retrigger of enable input OP Output switched off because of over temp...

Page 4: ... the rail 3 Slide it downward until it hits the stop 4 Press against the bottom for locking 1 2 3 4 DISMOUNTING 1 Pull down the slide clamp lever 2 Tilt the unit upward 3 Unhook the unit from the rail 1 2 3 FIG 5 RECOMMENDED CONNECTING CABLE Recommended Tightening torque 0 5 0 6 Nm 4 42 5 30 lbf in Solid 2 5 mm 12 AWG Stranded 1 5 mm 12 AWG L 6 0 7 5 mm 0 24 0 30 in FIG 6 INPUT PROTECTION Fuse MCB...

Page 5: ...VIRONMENT OPERATING TEMPERATURE DERATING 40 C to 70 C 5 95 r H non condensing 4 2 W C over 50 C Do not exceed Vout x Iout 100 W Max at 70 C NOTES Data may change without prior notice in order to improve the product Please refer to the latest version of the Installation Instruction for each product by visiting belfuse com power solutions ACCESSORIES LDX D20 20 A Active ORing controller LDX D50 50 A...