12 V / 24 V 20 A High Performance DC-UPS
25
NAME
SHORT NAME
VALUE
ALARM_BATTERY_UNDERTEMP_START
BUTS
Threshold temperature triggering the alarm.
Description
The measured battery temperature is lower than the alarm threshold. The threshold is the battery minimum temperature (§5.2.12).
NAME
SHORT NAME
VALUE
ALARM_BATTERY_UNDERTEMP_END
BUTE
The minumum battery temperature reached
during the alarm.
Description
The measured battery temperature returns above the alarm threshold.
NAME
SHORT NAME
VALUE
ALARM_BATTERY_RI_TOO_HIGH_START
Ri high start
None.
Description
The measured battery internal resistance exceeds the alarm threshold. The threshold is the battery nominal internal resistance (§5.2.9) +
maximal internal resistance variation (§5.2.10).
NAME
SHORT NAME
VALUE
ALARM_BATTERY_RI_TOO_HIGH_END
Ri high end
None.
Description
The measured battery internal resistance returns below the alarm threshold.
NAME
SHORT NAME
VALUE
ALARM_SHORT_CIRCUIT
Short circ.
None.
Description
A short circuit has been detected on the output.
NAME
SHORT NAME
VALUE
ALARM_BATTERY_ERROR
Batt. error
None.
Description
The LDX-U20 was unable to charge the battery correctly.