FLIPPING™ ARCH
1MANUL027
Belanger®, Inc. *PO BOX 5470 *Northville, MI 48167-5470 * Ph (248) 349-7010 * Fax (248) 380-9681
21
Installation
Utility Connections
Air
1. Locate the air panel in a dry location. See the image below.
Note:
The 4-Way Air Valve requires a 120VAC program function from the site controller.
2.
Run a 1/4” Poly-Flow air line from the main air supply to the Main Air Connection on the air
panel. See the images above and below.
3.
Run a 1/4” Poly-Flow air line from the extend regulator on the air panel to the extend port on
the Cylinder. See the images above and below.
4.
Run a 1/4” Poly-Flow air line from the retract regulator on the air panel to the retract port on
the Cylinder. See the images above.
Note:
Each port on the Cylinder has flow controls to adjust the cylinder actuation speed. See the
image above.
Extend Regulator Connection
1/4” Poly-Flow Tube to the Extend
Port on the Cylinder
Retract Regulator Connection
1/4” Poly-Flow Tube to the Retract
Port on the Cylinder
120 VAC Output from
the Site Controller
Retract Port
Speed Control for the Retract
Port on the Cylinder
Cylinder
Extend Port
Speed Control for the Extend
Port on the Cylinder
Head Assembly
4-Way Air Valve
Field Supplied 1/4" Poly Flow Tube
from the Main Pneumatic Source
@100 psi Air Flow Minimum
Field Supplied
1/4" Poly Flow Tube
Route as necessary
Air Panel
Extend Port
Retract Port
Main Air Connection
1/4” Poly-Flow Tube