28
Installation MACH104-PoEP
Release 10 09/2019
Proceed as follows:
Take the SFP transceiver out of the transport packaging (1).
Remove the protection cap from the SFP transceiver (2).
Push the SFP transceiver with the lock closed into the slot until it latches
in (3).
2.3
MACH104-16TX-PoEP-E...,
MACH104-16TX-PoEP+2X-E...:
Wiring and installation of the supply voltage
Note:
Note the safety instructions in
“Requirements for connecting electrical
WARNING
ELECTRIC SHOCK
Never insert sharp objects (small screwdrivers, wires, etc.) into the
connection terminals for electric conductors, and do not touch the terminals.
Failure to follow these instructions can result in death, serious injury,
or equipment damage.
WARNING
FIRE HAZARD
In the conductor to the voltage input, install an input fuse with a nominal
rating of max. 10 A – charakteristic B.
Use a cable cross-section of at least AWG17 (1 mm²) for the current
conductors at the voltage input.
Failure to follow these instructions can result in death, serious injury,
or equipment damage.