68
Installation
GRS1020
/112
0/10
30/11
30
Re
lease
04
01/2
020
EMC interference
immunity
Standard
applications
a
Merchant Navy
b
Railway
applications
(trackside)
c
Substation
applications
d
Electrostatic discharge
EN 61000-4-2
IEEE C37.90.3
Contact discharge
±4 kV
±6 kV
±6 kV
±8 kV
EN 61000-4-2
IEEE C37.90.3
Air discharge
±8 kV
±8 kV
±8 kV
±15 kV
Electromagnetic field
EN 61000-4-3
80 MHz ... 3000 MHz
max. 10 V/m
max. 10 V/m
max. 20 V/m
max. 10 V/m
IEEE 1613
80 MHz ... 1000 MHz
–
–
–
max. 35 V/m
Fast transients (burst)
EN 61000-4-4
IEEE C37.90.1
DC supply connection
±2 kV
±2 kV
±2 kV
±4 kV
EN 61000-4-4
IEEE C37.90.1
Data line
±4 kV
±4 kV
±2 kV
±4 kV
Voltage surges - DC supply connection
EN 61000-4-5
line/ground
±2 kV
±2 kV
±2 kV
±2 kV
IEEE 1613
line/ground
–
–
–
±5 kV
EN 61000-4-5
line/line
±1 kV
±1 kV
±1 kV
±1 kV
Voltage surges - data line
EN 61000-4-5
line/ground
±1 kV
±1 kV
±2 kV
±2 kV
Conducted disturbances
EN 61000-4-6
150 kHz ... 80 MHz
10 V
10 V
10 V
10 V
Summary of Contents for HIRSCHMANN GREYHOUND GRM Series