24
MACH 100
Release 04 07/10
2.1.4
“FAULT” signal contact
Figure 13: MACH 100 device, front view
1 - Signal contact
The signal contacts are connected via a 2-pin terminal block with screw
locking.
The signal contact (“FAULT”, for pin assignment of terminal block, see
fig. 14
) monitors the functioning of the device, thus enabling remote
diagnostics. You can specify the type of function monitoring in the
Management.
You can also use the Management to switch the signal contact manually
and thus control external devices.
A break in contact is used to report the following conditions via the potential-
free signal contact (relay contact, closed circuit):
The failure of at least one of the two voltage supplies
(voltage supply 1 or 2 is below the threshold value).
A continuous malfunction in the device (internal supply voltage).
The defective link status of at least one port. The report of the link status
can be masked by the Management for each port. In the default state, link
status monitoring is deactivated.
The temperature threshold value has been exceeded or has fallen below.
The removal of the ACA.
The following condition is also reported in RM mode:
Ring redundancy guaranteed. By default, there is no ring redundancy
monitoring
Connecting the terminal block
Pull the terminal block off the device and connect the signal lines.
Figure 14: 2-pin terminal block
1
FAULT