Installation MACH1000
Release 07 08/2022
41
2.3.2
Connecting the plugged voltage supply (power supply
units “L” and “M”)
Note:
Note the permitted voltage ranges for devices with
certification type “T” (EN 50155 railway (train) - see product code
position 38 in
table 1
).
Relevant for North America:
The torque for tightening the supply voltage terminal block on the device is
0.51 Nm (4.5 lb-in).
The terminal blocks for devices with power supply unit characteristic value M
or L are coded to prevent them from being accidentally connected to devices
with power supply unit characteristic value L or M.
Figure 15: Power supply unit supply voltage characteristic value L, DC voltage
(see
on page 52 “General technical data”)
Connecting
1 - Supply voltage
2 - Signal contact
WARNING
ELECTRIC SHOCK
Connect only a supply voltage that corresponds to the type plate of your
device.
Failure to follow these instructions can result in death, serious injury,
or equipment damage.
1
2
Relay
Summary of Contents for Hirschmann MACH1000 Series
Page 67: ...Installation MACH1000 Release 07 08 2022 67 ...
Page 68: ......