background image

6

Summary of Contents for Hirschmann OZD Profi 12M Pro Series

Page 1: ...07 CLASS 1 LASER PRODUCT LIGHT EMITTING DIODE CLASS 1LED PRODUCT Certified Usage Please observe the following Warning The device may only be employed for the purposes described in the catalog and technical description and only in conjunction with external devices and components recommended or approved by Hirschmann The product can only be operated correctly and safely if it is transported stored i...

Page 2: ... Tel 49 0 1805 14 1538 E Mail HAC Support Belden com FCC RULES This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 this device must accept any interference received including interference that may cause undesired operation Note This equipment has been tested and found to comply with the limit...

Page 3: ...the hazardous location temperature code When combining products within a system the most adverse temperature code lowest T number may be used to help determine the overall temperature code of the system Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation 䊳 The peripheral equipment must be suitable for the loca...

Page 4: ...orrect assignment can result in destruction of the repeater Limit values of relay contact Max switching voltage 60 V DC 42 V AC Max switching current 1 0 A Max switching capacity 30 W resistive load 䊳 The voltage connected to the relay must correspond to a safety extra low voltage SELV to IEC EN 60 950 and must comply with NEC Class 2 regulations as stipulated by UL CSA Analog Voltage Outputs The ...

Page 5: ...accordance with EN60079 15 taking into account the environmental conditions under which the equipment will be used 䊳 When the temperature under rated conditions exceeds 70 C at the cable or conduit entry point or 80 C at the branching point of the conductors the temperature specification of the selected cable shall be in compliance with the actual measured temperature values 䊳 Installation additio...

Page 6: ...6 ...

Page 7: ...ules 䡺 OZD Profi 12M P11 PRO 䡺 OZD Profi 12M G11 PRO 䡺 OZD Profi 12M G11 1300 PRO 䡺 OZD Profi 12M P12 PRO 䡺 OZD Profi 12M G12 PRO 䡺 OZD Profi 12M G12 1300 PRO 䡺 OZD Profi 12M G12 EEC PRO 䡺 OZD Profi 12M G12 1300 EEC PRO We apply the following network topology 䡺 Line topology with optical cable monitoring 䡺 Star 䡺 Line topology without optical cable monitoring 䡺 Redundant optical ring We use the fo...

Page 8: ...er Strasse 45 51 72654 Neckartenzlingen Germany Tel 49 0 1805 14 1538 E Mail HAC Support Belden com Internet http www hirschmann com We reserve the right to make technical modifications Hirschmann Automation and Control GmbH 2015 All Rights Reserved ...

Reviews: