8 Technical data
54
OZD Profi G12D... ATEX 1 V. 03 07/2014
OZD Profi G12 …
DU ATEX 1
DK ATEX 1
DE ATEX 1
Electromagnetic Compatibility (EMC)
Emitted immunity
Limit class A (EN 55022), FCC CFR 47 part 15, Class A
Interference immunity against static discharge
on shield connection and housing parts: ±4 kV contact discharge
(EN 61000-4-2)
Interference immunity against high
– 10 V/m at 80
%
amplitude modulation with 1 kHz,
frequency radiation
– 80 MHz - 1 GHz (EN 61000-4-3)
– 10 V/m with 50
%
duty cycle at 900 MHz (ENV 50204)
– 10 V/m at 80
%
amplitude modulation with 1 kHz,
–
10 kHz - 80 MHz
Interference immunity against conducted
On power supply lines and sheathed
disturbances (burst)
RS 485 bus cables: ±2 kV (EN 61000-4-4)
Interference immunity against conducted
– On power supply lines: ±1 kV symmetric
disturbances (surge voltage, surge)
– On sheathed RS 485 bus cables:: ±2 kV asymmetric
–
(EN 61000-4-5)
Climatic ambient conditions
Ambient temperature
– 20 °C to + 60 °C (IEC 60068-2-1, IEC 60068-2-2)
Storage temperature
– 40 °C to + 70 °C (IEC 60068-2-14)
Relative humidity
10
%
- 100
%
Air pressure
Operation: to 2000 m (795 hPa)
Transport and storage: to 3,000 m (700 hPa)
Pollution degree
2
Explosion protection
EC-type examination certification
PTB 09 ATEX 2044 X PTB 09 ATEX 2045
PTB 09 ATEX 2045
Fibre optic
inherent safe
Ignition protection
II 2 (1) G Ex mb e [ia] opis II, IIC, IIB T4/T6
-
II 2 (1) D Ex tD A21
II 2 (1) D Ex tD A21
IP 66 T 130 °C
IP 66 T 130 °C
Cable glands
Supply voltage
Number of glands
-
2
2
Diameter of gland
-
M 20
M 20
Permissible cable diameter
-
5.5 - 13 mm
5.5 - 13 mm
Signalling contact
Number of glands
-
1
Diameter of gland
-
M 16
M 16
Permissible cable diameter
-
5.5 - 10 mm
5.5 - 10 mm
RS 485 bus cable
Number of glands
-
2
2
Diameter of gland
-
M 16
M 16
Permissible cable diameter
-
5.5 - 10 mm
5.5 - 10 mm
Optical connections
Number of glands
-
2
2
Diameter of gland
-
M 20
M 20
Permissible cable diameter
-
6.4 - 13 mm
6.4 - 13 mm
Not used
Number of glands
-
1
1
Diameter of gland
-
M 16
M 16
Permissible cable diameter
-
5.5 - 10 mm
5.5 - 10 mm
Functional earth
-
fixed mount
fixed mount
connection
connection