10
Installation RS20/22/30/32/40
Release 03 06/2013
For the ground conductor, use a cable with a cross section of at least
1.0 mm².
Make sure there is at least 3.94 in (10 cm) of space in front of the
ventilation slits of the housing.
The device must be installed in the vertical position.
If installed in a living area or office environment, the device must be
operated exclusively in switch cabinets with fire protection
characteristics in accordance with EN 60950-1.
Environment
Only operate the device at the specified ambient temperature
(temperature of the surrounding air at a distance of up to 5 cm from the
device) and at the specified relative humidity.
When you are selecting the installation location, make sure you
observe the climatic threshold values specified in the technical data.
Use the device in an environment within the pollution degree specified
in the technical data.
Qualification requirements for personnel
Qualified personnel as understood in this manual and the warning signs,
are persons who are familiar with the setup, assembly, startup, and
operation of this product and are appropriately qualified for their job. This
includes, for example, those persons who have been:
trained or directed or authorized to switch on and off, to ground and to
label power circuits and devices or systems in accordance with current
safety engineering standards;
trained or directed in the care and use of appropriate safety equipment
in accordance with the current standards of safety engineering;
trained in providing first aid.
General safety instructions
This device is operated by electricity. You must follow precisely the
prescribed safety requirements for the voltage connections in this
document.
See “Supply voltage” on page 4.
See “Supply voltage for PoE power supply units (optional)” on page 5.