12
Installation RSP20/25/30/35
Release 18 09/2021
ATEX directive 2014/34/EU – specific regulations for safe
operation
Relevant for RSP devices when operating in explosive gas atmospheres
according to ATEX directive 2014/34/EU, the following applies:
List of standards:
EN IEC 60079-0:2018
EN 60079-7:2015 + A1:2018
EN IEC 60079-15:2019
Use only device variants featuring supply voltage with characteristic
value CC.
Make sure that the device has the following label:
II 3G Ex ec nC IIC T4 Gc
DEKRA 15ATEX0017X
Temperature class and code:
T4: 0 °C
≤
Ta
≤
+60 °C for “S” types or
T4:
−
40 °C
≤
Ta
≤
+70 °C for “T” or “E” types
(item 17 of nomenclature breakdown)
The equipment shall only be used in an area of not more than pollution
degree 2, as defined in IEC 60664-1.
The modules shall be installed in a suitable enclosure in accordance
with EN 60079-0 providing a degree of protection of at least IP54
according to EN 60529, taking into account the environmental
conditions under which the equipment will be used.
When the temperature under rated conditions exceeds 70 °C (158 °F)
at the cable or conduit entry point, or 80 °C (176 °F)at the branching
point of the conductors, the temperature specification of the selected
cable and cable entries shall be in compliance with the actual
measured temperature values.
Provisions shall be made to prevent the rated voltage from being
exceeded by transient disturbances of more than 119 V.
Connectors shall be connected or disconnected exclusively in dead-
voltage state.
Summary of Contents for HIRSCHMANN RSP20
Page 70: ......