Control Drawing for RSP devices according to Class I Division 2 Hazardous Locations
Rev.: 0
Document No.: 000189237DNR
Page 1/2
For Use in Hazardous Locations Class I Division 2 Groups A, B, C, D:
Only allowed for RSP 20/25/30/35 model No´s. which are individually labeled
“FOR USE IN HAZARDOUS LOCATIONS”.
Nonincendive fi eld wiring circuits must be wired in accordance with the National Electrical Code
(NEC), NFPA 70, article 501; CEC, Appendix J, Annex J18.
The earth conductor must be at least of the same wire size (mm² or AWG)
as the supply conductors.
WARNING – EXPLOSION HAZARD
Substitution of any components may impair suitability for hazardous locations or explosive
atmospheres.
WARNING – EXPLOSION HAZARD
Do not disconnect equipment unless power has been switched off or the area is known to be
known to be non-hazardous.