16
Installation RSP20/25/30/35
Release 18 09/2021
Control Drawing for RSP devices according to Class I Division 2 Hazardous Locations
Rev.: 0
Document No.: 000189237DNR
Page 2/2
Ordinary Location,
Non-Hazardous Area,
Non-Explosive Atmosphere
Explosive Atmosphere
Class I Division 2
Groups A, B, C, D
Hazardous Location
RSP
Relay
Power Supply unit type CC:
24 VDC - 48 VDC
Power Supply unit type K9:
110 VAC - 230 VAC or
60
VDC
-
250
VDC
Power Supply unit type KK:
2x 110 VAC - 230 VAC or
2x 60 VDC - 250 VDC
(Refer to the power supply code of the type designation on the device.)
Temperature Code: T4
Ambient Temperature rating:
Ta: 0 °C to +60 °C for “S” temperature types
Ta:
í
40 °C to +70 °C for “T” or “E” temperature types
(Refer to the temperature code of the type designation on the device.)
Relay contacts:
Equipment with nonincendive eld wiring parameters.
Polarity is not relevant.
The relay terminals are dependent upon the following
Entity parameters:
Ui
Ii
Ci
Li
30 V
90 mA
2 nF
1
H
Summary of Contents for HIRSCHMANN RSP20