Installation RSP20/25/30/35
Release 18 09/2021
2.5.1
Supply voltage with the characteristic value K9
You will find information on the characteristic values here:
“Device name and product code” on page 24
Figure 4: Supply voltage with the characteristic value K9: 3-pin terminal block with
screw locking
For the supply voltage to be connected, perform the following steps:
Remove the terminal connector from the device.
Connect the protective conductor with the clamp.
Connect the wires according to the pin assignment on the device with the
clamps.
Fasten the wires in the terminal block by tightening the terminal screws.
Type of the voltages
that can be
connected
Specification of the supply
voltage
Pin assignment
DC voltage
Rated voltage range DC:
60 V DC ... 250 V DC
Voltage range DC incl.
maximum tolerances:
48 V DC ... 320 V DC
+/L
Plus terminal of the supply voltage
-/N
Minus terminal of the supply
voltage
Protective conductor
AC voltage
Rated voltage range AC:
110 V AC ... 230 V AC,
50 Hz ... 60 Hz
Voltage range AC incl.
maximum tolerances:
88 V AC ... 265 V AC,
47 Hz ... 63 Hz
+/L
Outer conductor
-/N
Neutral conductor
Protective conductor
Table 7:
Supply voltage with characteristic value K9: type and specification of the
supply voltage, pin assignment
WARNING
ELECTRIC SHOCK
Install this device only in a switch cabinet or in an operating site with
restricted access, to which maintenance staff have exclusive access.
Failure to follow this instruction can result in death, serious injury, or
equipment damage.
N
L