Installation RSP20/25/30/35
Release 18 09/2021
59
8.3
EMC and immunity
You will find detailed information on the certificates and declarations applying
to your device in a separate overview.
See table 5 on page 26.
Stability
Standard
applications
Substation
applications
IEC 60068-2-6, test Fc
Vibration
—
2 Hz ... 9 Hz with
0.11 in (3 mm)
amplitude
5 Hz ... 8.4 Hz
with 0.14 in
(3.5 mm)
amplitude
5 Hz ... 8.4 Hz
with 0.14 in
(3.5 mm)
amplitude
8.4 Hz ... 150 Hz
with 1 g
9 Hz ... 200 Hz
with 1 g
—
200 Hz ... 500 Hz
with 1.5 g
IEC 60068-2-27, test Ea
Shock
15 g at 11 ms
15 g at 11 ms
EMC interference
emission
Standard
applications
Substation
applications
Radiated emission
EN 55032
Class A
Class A
DNV GL Guidelines
—
—
FCC 47 CFR Part 15
Class A
Class A
EN 61000-6-4
Fulfilled
Fulfilled
Conducted emission
EN 55032
AC and DC supply
connections
Class A
Class A
DNV GL Guidelines
AC and DC supply
connections
—
—
FCC 47 CFR Part 15
AC and DC supply
connections
Class A
Class A
EN 61000-6-4
AC and DC supply
connections
Fulfilled
Fulfilled
EN 55032
Telecommunication
connections
Class A
Class A
EN 61000-6-4
Telecommunication
connections
Fulfilled
Fulfilled
EMC interference
immunity
Standard
applications
Substation
applications
Electrostatic discharge
EN 61000-4-2
IEEE C37.90.3
Contact discharge
±4 kV
±8 kV
EN 61000-4-2
IEEE C37.90.3
Air discharge
±8 kV
±15 kV