INTUITY CONVERSANT System Version 6.0
MAP/100 New System Installation
585-310-176
Issue 3.0
June 1997
Getting Started
Page 1-2
Site Preparation
1
Site Preparation
This section describes physical requirements for the installation site, which
include:
■
Environmental considerations
■
Installation considerations
■
Weight and space considerations
■
Power requirements
Environmental Considerations
Place the MAP/100 in an area where the environmental conditions shown in
are maintained.
Installation Area Considerations
Observe the following when determining where to place the MAP/100.
■
Do
not
install the unit in an area with high-power electrical equipment.
■
Do
not
install the unit in the same area as copier machines because of the
paper particles created by such equipment.
■
Install the unit in an area that provides protection from excessive sunlight,
heat, cold, chemicals, static electricity, magnetic fields, vibration, dust,
and grime.
■
Maintain an air-distribution system that provides adequately cooled,
filtered, and humidity-controlled air.
NOTE:
The maximum heat output of a MAP/100 is approximately 2500 BTU.
Table 1-1.
Environmental Considerations
Operating State
Temperature
Humidity
Continuous Operation
+10 to +38
°
C
5 to 55%
noncondensing
Short-term operation
+10 to +38
°
C
5 to 80%,
noncondensing
Nonoperating
-40 to +60
°
C
5 to 95%,
noncondensing
1