Page 34
Page 35
BOILERMA
TE
2000
3.4 FAULT FINDING
Despite everyones best efforts some problems could occur and lead to complaints
from the householder.
Complaints can be grouped into the following three main categories:-
1. The system is noisy
2. Hot water service is unsatisfactory
3. Space heating is unsatisfactory
The following checks should be carried out by the installer before calling the
manufacturer.
1. Causes of a ‘Noisy’ System
Noisy pump operation
Check
the level of water in the F & E cistern - adjust and vent the pump/system
if necessary.
Check
the pump speed setting of the boiler pump - reduce if necessary but ensure
that the temperature rise across the boiler does not exceed 8°C.
Check
the pump speed setting of the heating pump - reduce if necessary but ensure
a temperature difference across the flow and return does not exceed 11°C.
Check
and adjust if necessary the heating system bypass valve.
Check
that the radiators are correctly balanced.
Noisy boiler operation
Check
the flow rate through the boiler at full gas rate by measuring the temperature
rise across the boiler. If the temperature rise is greater than 8°C, then increase
the pump speed.
Check
the level of water in the F & E cistern and the working head on the boiler.
Check
and vent the system if necessary.
Noise when hot water tap is opened
If the plate heat exchanger pump is noisy when the hot water tap is opened, then
check the level of water in the F & E cistern and vent the pump if necessary.
Water hammer - loose pipework and/or tap washers.
2. Causes of ‘Unsatisfactory Hot Water Service’
Check
that the BoilerMate is full of water i.e. level of water in the F & E cistern is
correct when system is cold.
Check
boiler thermostat - this should be set at maximum.
Check
that the boiler flow temperature is adequate when it stops firing. Boilers
should provide a flow temperature of 82 ± 3°C but temperatures as low as 76°C will
allow the BoilerMate 2000 to provide a satisfactory performance.
Check
that the store is charging to at least 75°C.
Check
that the hot water plate heat exchanger pump stops and starts when the
hot water tap is opened and closed.
Check
that the plate heat exchanger pump is set at maximum speed.
Check
that the space heating and hot water load is not greater than the boiler output
and that the BoilerMate 2000 model is suitable for the type of dwelling.
If all the above checks are satisfactory then it is possible that the performance of
the heat exchanger is impaired by scale. In this case the hot water flow rate will be
noticeably less than the cold water flow rate. Replace with a factory exchange unit
and re-check hot water performance.
3. Causes of ‘Unsatisfactory Space Heating’
Check
the boiler thermostat - this should be
set at maximum.
Check
that the boiler flow temperature before
it is switched off by its own internal thermostat
or the store sensor is adequate - it should not
be less than 80°C.
Check
the operation and the settings of
the heating programmer and the room
thermostat.
Check
that the heating system pump is
circulating the water to the radiator circuit.
If some rooms are not being heated properly,
then balance the system/check the operation
of the thermostatic radiator valves (if fitted).
Overflow from Feed and Expansion Cistern
Check
that the controlled level of water in the
cistern is no higher than necessary. Adjust
if required.
The ACB can be used to establish/check
the operating and set temperatures of the
appliance as well as identify faults on any
of the 3 sensors. This is done by operating
switches SW1 and SW2 as shown opposite and
reading the LED display. (See page 27)
Store T1, PHE T2, and DHW T3 indicate the
current value being read by the store, PHE
and DHW sensors respectively. The location
of the sensors is shown in the diagram shown
opposite/below.
T1 ON and T1 OFF show the store temperature
set points which are automatically reset on
each boiler cycle to match the temperature
produced by the boiler.
T1 ON shows the temperature at which the
store will call for heat, i.e signal the boiler to fire.
T2 OFF shows the temperature at which the
store will be satisfied, i.e signal the boiler to
switch off.
POWERFLUSHING/CLEANING OF THE HEATING
SYSTEM
If it is proposed to ‘powerflush’ the heating
system we would recommend that the
BoilerMate appliance is isolated from the
heating system being cleaned. Failure to do
this could seriously damage the appliance.
When carrying out the work always comply
fully with the manufacturers instructions for
the powerflushing equipment being used.
If in any doubt please consult our Technical
Helpline.
3.0 SERVICING
Summary of Contents for Gledhill BoilerMate 2000 125
Page 8: ...Page 8 1 0 DESIGN 1 2 TECHNICAL DATA...
Page 33: ...Page 33 BOILERMATE 2000 3 0 SERVICING...
Page 42: ......
Page 43: ......
Page 44: ......