Commissioning flow chart
14
Commissioning of the A-Isometer (2)
Connect the supply voltage
The A-ISOMETER carries out a
self test. The display indicates
the insulation value after finishing
the measurement.
Shall the basic setting
be changed?
Alarm1 = 40 kOhm
Alarm2 = 10 kOhm
K1/K2 = N/O operation
Memory = off
no
yes
Does one of the alarm LEDs
light up?
Select
ISO SETUP
(see chapter operation and setting)
no
yes
The insulation value of the system
being monitored is below the preset
response value. Change the response
value or improve the insulation
condition of the system.
Connect the voltage of the
system to be monitored
Summary of Contents for A-ISOMETER IR1570 Series