Basic programs
56
VMD460-NA_D00001_05_M_XXEN/01.2020
Explanatory notes to "4110" settings
1)
Relay mode:
NC:
The relay is
energised
in
normal operation
and deenergised in the alarm state
NO
:
The relay is
deenergised
in
normal operation
and energised in the alarm state
2)
Not used for VDE-AR-N 4110:2018-11
3)
Profile naming Refer to "Basic programs" on page 49.
4. df/dt
Exit
1. Function
off; on
off
off
off
off
2. Resp. value
0.05…9.95 Hz/s
1.00 Hz/s
1.00 Hz/s
1.00 Hz/s
1.00 Hz/s
3. Hysteresis
1.0…50.0 %
20.0 %
20.0 %
20.0 %
20.0 %
4. Meas. window
50 ms…1 s
200 ms
200 ms
200 ms
200 ms
5. t
(OFF)
40 ms…60 min
100 ms
100 ms
100 ms
100 ms
6. t
(ON)
off 40 ms…60 min
off
off
off
off
5. Vect.shift
Exit
1. Function
off; L1; L2; L3; single; all
off
off
off
off
2. Resp. value
1.0…25.0 °
8.0 °
8.0 °
8.0 °
8.0 °
3. t
(START-UP)
off; 40 ms…60 min
2.00 s
2.00 s
2.00 s
2.00 s
4. t
(ON)
off; 40 ms…60 min
off
off
off
off
6. Unbalance
Exit
1. Function
off; on
off
off
off
off
2. Resp. value
1.0…50.0 %
5.0 %
5.0 %
5.0 %
5.0 %
3. Hysteresis
1.0…50.0 %
20.0 %
20.0 %
20.0 %
20.0 %
4. t
(OFF)
40 ms…60 min
100 ms
100 ms
100 ms
100 ms
7. Relays
Exit
1. Relay mode
1)
NC; NO
K1: NC
K2: NC
K1: NC
K2: NC
K1: NC
K2: NC
K1: NC
K2: NC
8. Dig. input
Exit
1. Mode
NC; NO; off
D1: off
D2: off
D3; D4: ––
2)
D1: off
D2: off
D3; D4: ––
2)
D1: off
D2: off
D3; D4: ––
2)
D1: off
D2: off
D3; D4: ––
2)
2. t
(START-UP)
40 ms…60 min
D1: ––
D2: ––
D3; D4: ––
2)
D1: ––
D2: ––
D3; D4: ––
2)
D1: ––
D2: ––
D3; D4: ––
2)
D1: ––
D2: ––
D3; D4: ––
2)
3. Fault memory
off; on
D1: off
D2: off
D3; D4: ––
2)
D1: off
D2: off
D3; D4: ––
2)
D1: off
D2: off
D3; D4: ––
2)
D1: off
D2: off
D3; D4: ––
2)
4110 Menu :
once twice
Profile 1
3)
Profile 2
3)
Profile 3
3)
Profile 4
3)