Installation and connection

14

VG12_D00032_03_M_XXEN/01.2019

4.2   Connection

The VG12 is connected via a plug connection:

 

Connect the Schuko plug connecting cable of the VG12 safety distributor to a 
Schuko socket-outlet of the power generator.

DANGER

Risk of an electric shock!

Work activities on electrical parts of the power generator and on the 
electrical equipment must only be carried out by electrically skilled 
persons.

WARNING

Danger due to freely accessible generator socket-outlets!

Use the socket-outlets of the VG12 safety distributor only. 
Any other socket-outlets of the power generator must be shut down. 
When the socket-outlets have been shut down and closed by means of 
a protective cap, secure the socket-outlets with a locking wire against 
unauthorised use.

CAUTION

Danger due to excessive nominal system voltage!

VG12 is only suitable for power generators with AC 230 V. Higher
voltages may destroy components of the safety distributor. Hence, the
protective function may be disabled. 

Summary of Contents for B980853

Page 1: ...EN Manual VG12 Safety distributor for mobile power generators ready for connection VG12_D00032_03_M_XXEN 01 2019...

Page 2: ...o KG P O Box 1161 35301 Gr nberg Germany Londorfer Stra e 65 35305 Gr nberg Germany Tel 49 6401 807 0 Fax 49 6401 807 259 E mail info bender de www bender de Bender GmbH Co KG All rights reserved Repr...

Page 3: ...7 2 4 General safety instructions 7 3 System description 8 3 1 Protective measures for mobile generators 8 3 2 Prerequisites for use 8 3 3 Functional description 9 3 3 1 Display and operating element...

Page 4: ...Table of Contents 4 VG12_D00032_03_M_XXEN 01 2019 6 Technical data 19 6 1 Standards and certifications 21 6 2 Ordering details 22 6 3 Other safety distributors 22 INDEX 23...

Page 5: ...ave any questions please do not hesitate to contact us In this case please refer to our service www bender de en service support downloads 1 2 Explanation of symbols and notes The following symbols to...

Page 6: ...d in order to be able to apply the protective measure 2 2 Work activities on electrical installations Only electrically skilled persons are permitted to carry out the work necessary to install commiss...

Page 7: ...anger safety Do not make any unauthorised changes and only use replacement parts and opti onal accessories purchased from or recommended by the manufacturer of the devices Failure to observe this requ...

Page 8: ...whole generator circuit must be connected by insulated unearthed protective equipotential bonding conductors PA see schematic wiring diagram on Page 15 Such conductors must not be connected to the pro...

Page 9: ...ects the VG12 safety distributor to the power generator The VG12 safety distributor contains an insulation monitoring device in accordance with EN 61557 8 It is an actively measuring ISOMETER type IR4...

Page 10: ...tlets If both sockets are used the total nominal current of both sockets must not exceed 16 A 3 Insulation monitoring device IR423 4 Instruction for daily test 5 Combined test reset button T R Achtung...

Page 11: ...p if the value falls below the response value Ran2 Alarm 2 prewarning 4 The test button T is intended for the daily test of the safety distributor After pressing it AL1 and AL2 light up 5 The insulati...

Page 12: ...they are not destroyed by the typical vibrations of the power generator Avoid sharp edges and corners Secure the mounting screws via lock washers spring washers or the like 4 1 1 Dimension diagrams Fi...

Page 13: ...Installation and connection 13 VG12_D00032_03_M_XXEN 01 2019 Fig 4 2 Dimensions of the VG12 130 180 mm 96 ca 40 mm 163 mm 113...

Page 14: ...ectrically skilled persons WARNING Danger due to freely accessible generator socket outlets Use the socket outlets of the VG12 safety distributor only Any other socket outlets of the power generator m...

Page 15: ...rms you about the interaction of the components ge nerator VG12 safety distributor and loads The details are purely informative and not re quired for the connection of the VG12 to the power generator...

Page 16: ...t reset button T R of the VG12 A short time later tES appears on the display for a few seconds In the following the alarm LEDs AL1 and AL2 light up and the VG12 disconnects all poles of the safety soc...

Page 17: ...the VG12 safety distributor 3 Press the combined test reset button T R of the VG12 for 3 s A short time later tES appears on the display for a few seconds In the following the alarm LEDs AL1 and AL2...

Page 18: ...reset button T R was pressed deliberately or acci dentally Press the combined test reset button T R for 1 s LEDs AL1 AL2 light up no loads connected Insulation fault power generator Turn off power ge...

Page 19: ...elay ton 0 99 s 0 s Measuring circuit Measuring voltage Um 12V Measuring current Im at RF 0 200 A Internal resistance DC Ri 62 k Impedance Zi at 50 Hz 60 k Permissible extraneous DC voltage Ufg DC 300...

Page 20: ...60721 3 3 3M4 Transport IEC 60721 3 2 2M2 Long term storage IEC 60721 3 1 1M3 Vibration resistance acc to IEC 60068 2 6 DIN rail 3 g 30 150 Hz Screw mounting 6 g 30 150 Hz Connection Socket outlets In...

Page 21: ...ecial installations or locations Construction and demolition site installations DIN VDE 0100 100 VDE 0100 100 Low voltage electrical installations Part 100 Application area purpose and principles DVGW...

Page 22: ...iented protective measures Protective separation with insulation monitoring and shutdown Type Nominal voltage Un Order number VG12 Safety distributor for mobile power generators ready for connection A...

Page 23: ...ional test before first use 16 H How to use this manual 5 I Installation 12 Intended use 6 O Ordering details 22 Other safety distributors 22 R Regular tests 18 S Safety instructions device specific 7...

Page 24: ...ives and bendersystembau archives Bender GmbH Co KG P O Box 1161 35301 Gr nberg Germany Londorfer Stra e 65 35305 Gr nberg Germany Tel 49 6401 807 0 Fax 49 6401 807 259 E mail info bender de www bende...

Reviews: