18 CC613-Hxx_D00423_02_M_XXEN/11.2020
Connection
• inepro PRO1/PRO2/PRO380
• NZR EcoCount S85
• Optec
• Phoenix Contact EEM-MB371 (TCP)
• Saia ALE3
• Siemens 7KT1666/7KM2200 (TCP)
Meter Slave ID
Baud rate
Parity
Data Bit
Stop Bit
1
9600
N (none) (except Saia) -> even
8
1
Additional Modbus meters can be included in future software updates upon customer request. Refer to the
Manufacturer
tab on the web server for a list of supported Modbus meters.
The Modbus meter interface is terminated with a terminating resistor of 120 Ω.
i
With use of a Modbus TCP meter it is possible to read the energy demand of external consumers (e.g. resi-
dential buildings). Depending on this, the maximum charge current can be set.