Installation, connection and commissioning
23
CMD420_421-DM_D00224_01_M_XXEN/08.2016
4.3
Commissioning
Checks must be carried out prior to commissioning to ensure that the current
monitoring device has been connected correctly. Then perform a functional
test.
Incorrect connections can lead to personal injury and
damage to equipment or property!
The maximum permissible measuring current and the
overload capability of the measuring inputs k, l have to be
taken into consideration!
1
2
3
Connect the conductor to the push-wire ter-
minals according to the schematic diagram.
Terminal Connections
A1, A2
Connection to supply voltage
k1, l1
k2, l2
k3, l3
Connection to the conduc-
tors to be monitored using
current transformers
M+
(common) positive pole of
the analogue interface
μA
Current output 0…400 μA
mA
Current output 0/4…20 mA
V
Voltage output 0…10 V
CAUTION