Operation and configuration
30
CMD420_421-DM_D00224_01_M_XXEN/08.2016
5.5
Display in menu mode
5.5.1
Parameter query and setting: overview
Menu
item
Adjustable parameter
AL
Response value query and setting:
– Alarm I2 (AL2), (undercurrent, overcurrent or window
function can be set in the SEt/I menu)
– Prewarning I1 (AL1), (X % of I2)
– Specify the hysteresis of the response values: Hys I12
out
Configure the fault memory and the alarm relays:
– Activate/deactivate the fault memory or select con
mode
– Select output signal (I/U)
– Select 100% reference related to the output signal (AnA)
t
– Start-up delay
t
Set
Set parameters for device control:
– Select the appropriate parameter for response values:
overcurrent (HI), undercurrent (Lo) or window function
(In)
– Set the transformation ratio (n) for the current transfor-
mer
– Activate or deactivate password protection, change
password
– Restore factory settings
– Service menu SyS blocked
InF
Query software version
HiS
Query the alarm value saved first
ESC
Go to the next highest menu level (back)