Function
19
CMD420_421-DM_D00224_01_M_XXEN/08.2016
either be set within the response value range listed in the table or can be set
in relation to the response value I2.
The column "Display" in the table above shows the phase-related measure-
ment possibilities. In the column "measuring quantity" the displays are explai-
ned. The column "100-% value" shows details about the setting range or
configuration in relation to the response value.
The setting of the analogue interface via the menu is described from page 35
onwards.
3.2.10 Password protection (on, OFF)
With the password protection activated (on), settings can only be made sub-
ject to the correct password being entered (0…999).
3.2.11 Factory setting FAC
After activating the factory setting, all previously changed settings are reset to
delivery status.
3.2.12 Transformation ratio of the current transformers
The transformation ratio for the current transformers has to be set as factor
n
in the menu "Set".
CMD420-DM requires current transformers with a transformation ratio of
n
= x/1A.
CMD421-DM requires current transformers with a transformation ratio of
n
= x/5A.
The actual primary current can be calculated by multiplying the measured
current by factor
n
and indicated on the display.
Transformation ratio
Resolution of
the display
Factor
n
Resolution of the settings
1…9
1
0,01 A
10…99
1
00.1 A
100…990
10
001 A
1.00…2.00 k
0.05 k
0.01 kA